ADTRAN 61175044L2-22B Battery Backup Unit, Battery Specifications, Maintenance, for remedy

Models: 61175044L2-22B

1 2
Download 2 pages 15.46 Kb
Page 2
Image 2
BATTERY

BATTERY

BATTERY BACKUP UNIT

JOBAID

61175044L2-22B

 

 

MOUNTING INSTRUCTIONS

BATTERY SPECIFICATIONS

 

BACKUP

UNIT

P/N: 1175044L2

CLEI: SIMPBBBARA

1

Unpack the Total Access 750/ 850 Battery Backup Unit and inspect

for damage. If damage is apparent, refer to your carrier or supplier

 

for remedy.

 

Note: It is not necessary to remove the batteries during

 

installation process.

2

The battery box must be mounted with the following minimum

clearances:

 

Top-9" (for Total Access 750/850)

 

Top- 5" (for Total Access 612/616/624)

 

Left Side-5"

 

Right Side-1”

 

Bottom-3"

3

Using the template provided, mark and drill three pilot holes for #10

mounting screws.

4

Insert #10 x 3/ 4" flat- head wood screws (supplied) into the three

pilot holes, leaving 1/ 16" space between the screw- head and the

Batteries: 7 Amp/ hr (4 batteries per pack)

Case size: 6" W x 3 3/ 4" H x 2 1/ 2" D

Battery type: Lead acid

Voltage: -54 VDC

Backup Time: Up to 8 hours

Wire Gauge: 18 AWG

Preferred Temperature: 68º F (20º C)

The device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Changes or modifications not expressly approved by ADTRAN could void the user's authority to operate this equipment.

1175044L2

BATTERY BACKUP

-48 VDC

Note: Battery Backup Unit is designed for use with the Total Access 612, 616, 624,

 

backboard.

 

CAUTION: Fully loaded Battery box weighs 30 lbs.

5

Mount the battery box on the three support screws on the backboard.

6

cover.Remove the two closure screws on the battery box and open the

7

Use a long shaft screwdriver to tighten the three support screws.

Note: The connection for the Total Access 850 will be identical to the Total Access 750.

CAUTION!

During

Total Access 750 wall installation, position the chassis so front panels face up.

Total Access 750

V.35

WARNING:

T1

Terminal P2

20 Hz FUSE

MUST BE REMOVED

 

 

LX IN

 

access

BEFORE REMOVING COVER.

 

R1-I

LY IN

 

cover

 

FT1

T1-I

EU2

 

R-O

LX OUT

 

 

T-O

LY OUT

 

 

 

EU1

 

 

 

MLT-A

MANAGEMENT

 

MLT-B

 

-48ALM

 

 

 

MJ

 

 

-48 R

MJR

 

DC

 

MJV

 

-48 V

MJVR

 

POWER

 

 

-54 VDC Output to Total Access 750

To Alarms

750 and 850 units.

WARRANTY

 

 

Warranty for Carrier Network products manufactured by ADTRAN and

supplied under Buyer's order for use in the U. S. is ten (10) years, except

for batteries which carry manufacturer's warranty. For a complete copy of

ADTRAN's U. S. Carrier Network Equipment

Warranty: (877) 457- 5007, Document 414.

TELECOMMUNICATIONS CODES

Code

Input

Output

IC

C

TC

1175044L2

BATTERY BACKUP

AC/DC Power Supply

120VAC/

-54VDC

AC ALARM

 

BATTERY

 

2A 60HZ INPUT OUTPUT

 

Battery Charging Unit

 

INPUT

OUTPUT

 

 

 

P/N: 1175043Lx

GROUND

+ -

 

AC Power Input

-54 VDC Battery

Charging/Discharging Line

 

CAUTION

During wall installation, position the Total Access 612/616/624 as shown in 61200624L1-19A.

C A U T I O N !

SUBJECT TO ELECTROSTATIC DAMAGE

PC

E

MAINTENANCE

-48 VDC

9902271

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

Life expectancy: 3- 5 years on standby use

Battery performance is adversely affected by extreme emperatures.

Old barreries should be recycled. Reference 60000120-36A for further information.

Total Access 612/616/624

AC Power Input

JOBAid, 61175044L2-22B, December 2002

Technical Support 1-888-4ADTRAN (1-888-423-8726)

Copyright 2002 ADTRAN, All Rights Reserved

Page 2
Image 2
ADTRAN 61175044L2-22B Battery Backup Unit, Battery Specifications, Maintenance, P/N 1175044L2 CLEI SIMPBBBARA, for remedy