AEG 160-500kVA manual Protect 8.33 Specification, Three Phase Output

Models: Protect 8.33 160-500kVA

1 4
Download 4 pages 5.99 Kb
Page 3
Image 3

Protect 8.33: Specification

Three Phase Output

MODEL

P8.33-160

P8.33-220

P8.33-330

P8.33-400

P8.33-500

NOMINAL RATING (AT COS φ 0.8 LAG)

 

 

 

 

 

IN KVA

160

220

330

400

500

RECTIFIER UNIT

 

 

 

 

 

 

 

 

 

 

Input nominal voltage

 

3 X 400 V (3 X 380 V, 3 X 415 V)

 

 

Input operating range (min/max)

 

 

340 V–460 V

 

 

Frequency

 

 

50/60 Hz ±10%

 

 

Input current in A at nominal load

259

357

535

649

811

Charging characteristic to IEC 478-10

 

 

IU

 

 

Nominal DC voltage

 

 

384 V

 

 

Rectifier type

 

 

 

 

 

- Standard

6 pulse

12 pulse

12 pulse

12 pulse

12 pulse

- Optional

12 pulse

 

 

 

 

INVERTER UNIT

 

 

 

 

 

 

 

 

 

 

 

DC input

 

 

384 V ± 20%

 

 

Nominal AC voltage

 

3x 400 V (3 x 380 V, 3 x 415 V)

 

 

Output voltage static response

 

 

< ±1%

 

 

Output voltage dynamic response

 

 

< ±2%

 

 

Recovery time

 

 

2 ms

 

 

Frequency

 

 

50/60 Hz

 

 

Frequency tolerance without mains

 

 

±0.1%

 

 

Frequency synchronisation range

 

 

±1% (±2%, ±3%)

 

 

Allowable load power factor

 

 

0.0 lag to 0.0 lead

 

 

Output phase current in A

231

318

477

578

723

Voltage wave form

 

 

sinusoidal

 

 

Voltage distortion

 

 

<3%

 

 

Crest factor

 

 

max. 3

 

 

Overload response 1 min.

 

 

150%

 

 

Overload response 10 mn.

 

 

125%

 

 

Max short circuit current

 

 

> 3 x I nom

 

 

STATIC BYPASS SWITCH

 

 

 

 

 

 

 

 

 

 

AC voltage

 

3 X 400 V (3 X 380 V, 3 X 415 V)

 

 

Frequency

 

 

50/60 Hz

 

 

Nominal power in kVA

160

220

330

400

500

GENERAL DATA

 

 

 

 

 

 

 

 

 

Efficiency (AC to AC) – typical

 

up to 94% / >98% with ECO-Mode

 

Noise level depending on rating

 

 

up to 74dB(A)

 

 

EMC compatibility

 

 

EN 62040-2

 

 

Air cooling with redundant and monitored fans

 

Yes

 

 

Operating temperature range min./max.

 

 

 

 

 

(without de-rating)

 

 

–5°C / +40°C

 

 

Storage temperature range min./max.

 

 

–30°C / +75°C

 

 

Maximum altitude without de-rating

 

 

1000 m

 

 

Protection degree IEC 529/EN 60529

 

 

 

 

 

standard system

 

IP20, IP22 & IP43 (>IP43 engineered)

 

Equipment colour

 

 

RAL 7035

 

 

WEIGHTS AND DIMENSIONS

 

 

 

 

 

 

 

 

 

 

 

Height standard UPS (mm)

1910

1915

1915

1915

1915

Height with max. options (mm)

2015

2210

2210

2210

2210

Width (mm)

1800

2100

3300

3300

3300

Depth (mm)

960

960

960

960

960

Weight (kg)

2410

2900

3970

4380

4980

Page 3
Image 3
AEG 160-500kVA manual Protect 8.33 Specification, Three Phase Output