5.1Specifications

MODEL

 

PROTECT A. 500

 

PROTECT A. 700

 

 

 

 

 

Type power

 

500 VA / 300 W

 

700 VA / 420 W

 

 

 

 

UPS-input

Input voltage

220 Vac / 230 Vac / 240 Vac

 

 

 

 

Input voltage range

150 – 280 Vac

 

without battery mode

 

 

 

 

Frequency (auto

50 / 60 Hz ± 5 Hz

 

selection)

 

 

 

UPS-output

Rated output voltage

220 Vac / 230 Vac / 240 Vac

 

/AVR-technology

 

 

 

 

Rated output voltage

 

±10%

 

in battery mode

 

 

 

 

Frequency in battery

50 / 60 Hz ± 1 Hz

 

mode

 

 

 

 

Transfer time at mains

2 – 6 ms (typical)

 

outage

 

 

 

 

Output Waveform

Modified sinewave

 

 

 

 

 

Battery

Type

12 V / 7 Ah x 1

 

12 V / 9 Ah x 1

 

 

 

 

 

 

Autonomy time

 

2 min

 

(full Load)

 

 

 

 

Recharge time (to

 

8 h

 

90% of rated capacity)

 

 

 

Indicator

AC mode

Green LED lighting

 

 

 

 

Backup mode

Yellow LED flashing

 

 

 

 

Fault

Red LED lighting

 

 

 

Acoustic alarm

Backup mode

Sounding every 10 seconds

 

 

 

 

Low battery

Sounding every second

 

 

 

 

Overload

Sounding every 0.5 second

 

 

 

 

Battery replacement

Sounding every 2 seconds

 

 

 

 

Fault USP

Continuously sounding

 

 

 

 

 

Protection

 

Discharge, overcharge, and overload protection

 

 

 

 

 

General data

Size W x H x D (mm)

100 x 140 x 330

 

 

 

 

 

 

Weight (kg)

6 kg

 

6,5 kg

 

 

 

 

 

Operating temperature

0°- 40°C

 

 

 

 

 

range

Relative humidity: 0 – 90 % (non-condensing)

 

 

 

 

Audible noise

< 40 dB (A)

 

(1 m distance)

 

 

 

Communication

Interfaces

USB and RS232 for status and measurement levels

 

 

 

 

Shutdown-Software

Included for all typical operating systems

 

 

 

 

 

(on CD)

(e.g. Windows, Linux, Mac)

 

 

 

 

 

16