In case of the Power Controller type 2P, the voltage transformers output the voltages L1-L2 and
L3-L1. To achieve a good resolution of the voltage measurement, 3 measuring ranges are provided. Selection of the ranges is performed by means of 4-pin bars, which have been set to the Power Controller type voltage by the works. The pin bars are found on the control device A70 above the terminal X7.
MAINS | SHORT CIRCUIT JUMPERS | MAX. |
VOLTAGE | X501, X502, X503 | MEASURING |
230V | 1 - 2 | 253V |
400V | 2 - 3 | 440V |
500V respectively 690V | 3 - 4 | 760V |
TAB. 17 VOLTAGE MEASUREMENT JUMPER
If the jumpers are changed, then a change of parameters is required.
Hardware parameters
Type | voltage | U_TYP |
U eff | max | UEMA |
X501-3,1-2,2-3,3-4 | TYP-BEREICH |
Mains voltage | U_NETZ_ANW |
| | (Thyro-Tool Family) |
REMARK
Voltage readings in not-controlled phases
Thyro-P 2P
Although phase 2 is not controlled with Thyro-P 2P, it is possible to take measuring values during this phase. The voltage transformer suitable for standard rail assembly (order no. 2000000399) is to be used. Connection is made as in table 21 to X7.1.26 – X7.2.25. The maximum induced voltage of the transformer (incl. over-voltage) must be less than 50 volts.
Thyro-P 1P
As only phase 1 is controlled with Thyro-P 1P, the reading systems of phase 2 and 3 can be used freely. The voltage transformer suitable for rail assembly (order no. 2000000399) is to be used. Connection is made as in table 23 to terminals X7.1.26 – X7.2.25 for “phase 2” and X7.1.36 – X7.2.35 for “phase 3”.
The measuring values do not influence the controller and are available for Bus interfaces, display and analog outputs. Parameter values must not be changed.
4.12 OTHER CONNECTIONS AND TERMINAL STRIPS
| ROOT* | BREAK CONTACT | CLOSER |
Alarm relay K1 | X2.7 | X2.8 | X2.9 |
Limiting K2 | X2.10 | X2.11 | X2.12 |
Option K3 | X2.13 | X2.14 | X2.15 |
* tie point