32
3.1.4 COPYING FUNCTION USING THE LBA
It is possible to load the complete user-specific data record (parameters) of a Power Controller
(for instance no. 1) into the memory of the LBA (RAM), store it in the LBA (EEPROM) and then
copy it into another Power Controller (for instance no. 2):
PLUG LBA INTO POWER CONTROLLER NO. 1
1. reload data (data is stored in the LBA RAM)
2. storing in the LBA
(data is copied into the LBA-EEPROM)
After the waiting time unplug LBA from Power Controller 1.
Plug LBA into Power Controller no. 2
3. LBA -> Thyro-P
After the waiting time data from LBA are in Power Controller 2.
4. Save Thyro-P
TAB. 7 COPYING FUNCTION USING THE LBA
Data from Power Controller 1 have now been copied to Power Controller 2.
ATTENTION
Only parameters of equal Power Controllers (for instance type voltage, type current, phase
number) may be copied.
3.1.5 OPERATION DISPLAY
On the operation display, one, two or three actual values are optionally displayed in double digit
size. An example for the operation display able to be configured using parameters is shown
below:

U1 456.7V

I1 1567.9A

PG 1234.8kW

Status messages

FIG. 7 OPERATION DISPLAY
The operating data displayed are the values U, I and P (Pges for 3-phase system) of phase 1. It is
also possible to display data of other phases. The lowest line is the status line; this is where the
device configuration is displayed, if no indications are waiting. Otherwise, „status messages“ is
displayed. By selecting the key, the indications are displayed:

Status messages ^v

yyyymmdd hhmmss

limit 1250kW

yyyymmdd hhmmss

undervoltage <360V

fault type, load, Power
Controller type, limitations,
etc. are notified with the
corresponding time of day. etc.