10. SPECIFICATIONS

TYPE VOLTAGE

...P400...

 

230 volts -20%

to

400 volts +10%

 

...P500...

 

230 volts -20%

to

500 volts +10%

 

...P690...

 

500 volts -20%

to

690 volts +10%

 

 

 

 

 

 

MAINS FREQUENCY

all models

 

45Hz to 65Hz

 

 

LOAD DESCRIPTION

ohmic load (minimum 100W)

 

 

 

ohmic load Rhot/Rcold ratio up to 20 (MOSI operation)

 

transformer load

 

 

TRANSFORMER

The induction of the load side transformer should not exceed

 

1.45T in case of mains overvoltage when using grain-oriented,

 

cold-rolled plates. This corresponds to a nominal induction of

 

approx. 1.3T.

 

 

 

OPERATING MODES

TAKT = full oscillation clock principle = default setting for the

 

 

 

models 1P, 2P and 3P

 

 

 

VAR = phase-angle control = only for the models 1P and 3P

 

SSSD = soft-start-soft-down; a combination of

 

 

 

 

„VAR“ und „TAKT“, for the models 1P, 2P and 3P,

 

 

 

i.e. reduced mains surge load

 

SET POINT INPUTS

The Power Controller Thyro-P has 4 set point inputs.

 

The set point inputs are indirectly connected to the mains

 

(SELV, PELV).

 

 

 

 

Set points 1, 2: external set point input

 

 

signal ranges:

 

 

 

 

0(4)

-

20

mA

Ri about 250 max. 24mA*

 

0

-

5

V

Ri about 8,8k max. 12V

 

 

0

-

10

V

Ri about 5k

max. 12V

 

 

* refer to ”ATTENTION” on page 16

 

 

Set point 3: connection for fibre optic (LL) from the wuper-

 

ordinate PC or automation system

 

 

 

Set point 4: set point assignment via RS 232 (for instance LBA)

 

The four set points are added internally and the total of the

 

set points, for instance for power control, is proportionate to

 

output power. For set point 2, there are different valuation

 

options: it may be added to set point 1 or subtracted from set

 

point 1.

 

 

 

 

 

 

 

ANALOG OUTPUTS

3 outputs: signal level 0-10 volts, 0-20mA or parameters may be

 

set differently. The maximum burden voltage is 10V

CONTROL CHARACTERISTIC

The control characteristic is established by the maximum value

 

of the dimensions to be controlled and the key values of the

 

set point. Using these key values, the linear control characte-

 

ristic may be set at will.

 

 

 

Every controller (for instance temperature controller), whose

 

output signal is in the range of 0-20mA/0-5V/0-10V may be

 

easily adapted to the Power Controller.

 