69

TABLE TERMINAL SCREWS

THYRO-P 1P, 2P, 3P

CONNECTOR

 

EARTHING SCREW

 

 

 

 

 

U1, V1, W1, U2, V2, W2

 

37H, 75H

M 6

 

M 6

 

80H

 

M 8

 

M 10

 

110H

M 6

 

M 6

 

130H, 170H

M 8

 

M 10

 

200HF, 280HF, 300HF

M 10

 

M 10

 

495HF, 500HF, 650HF

 

 

 

 

780HF, 1000HF, 1400HF,

M 12

 

M 12

 

1500HF, 1700HF, 1850HF,

 

 

 

 

2000HF, 2100HF, 2200HF,

 

 

 

 

2400HF, 2600HF, 2750HF,

 

 

 

 

2900HF

 

 

 

 

 

 

WITH UL APPLICATIONS

POWER CONNECTION

USE ONLY 60°/75°C COPPER CONDUCTORS (UL SPECIFICATION)

STUD TORQUE FOR

SCREW

MIN

RATED

MAX

TABLE TERMINAL SCREWS

M

2

0.2

0.25

5.9

[Nm]

M

6

3.0

4.4

22.5

 

M

8

11.5

17.0

44

 

M 10

22.0

33.0

75

 

M 12

38.0

56.0

75.0

[Pound inches]

SCREW

MIN

RATED

MAX

 

M

2

1.9

2.2

2.5

 

M

6

26.1

38.9

52.2

 

M

8

101.8

150.5

199.1

 

M 10

194.7

292.1

389.4

 

M 12

336.3

495.6

663.8

VENTILATOR 230 V, THYRO-P (HF-TYPES)

TYPE CURRENT

AIR VOLUME

SOUND PRESS.

50-60 HZ

50HZ

60HZ

[M3/H]

IN 1 M DIST.

 

 

I [A]

I [A]

[DBA]

 

1P

 

 

 

 

 

200HF, 280HF

0.22

0.22

120

53

 

300HF, 495HF, 500HF, 650HF

0.50

0.38

150

67

 

780HF, 1000HF, 1400HF, 1500HF

0.55

0.60

580

75

 

2000HF, 2100HF, 2600HF, 2900HF

1.00

1.20

2200

81

 

2P

 

 

 

 

 

200HF, 280HF

0.50

0.38

200

67

 

300HF, 495HF, 500HF, 650HF

0.50

0.38

230

67

 

780HF, 1000HF, 1400HF, 1500HF

1.00

1.20

1200

81

 

1850HF, 2000HF, 2400HF, 2750HF

1.00

1.20

2100

81

 

3P

 

 

 

 

 

200HF, 280HF

0.50

0.38

260

67

 

300HF, 495HF, 500HF, 650HF

1.20

0.85

450

72

 

780HF, 1000HF, 1400HF, 1500HF

1.00

1.20

1600

81

 

1700HF, 1850HF, 2200HF, 2600HF

1.00

1.20

2000

81

The ventilators (with HF types) must run with Thyro-P switched on. Connection according to connecting diagrams.

Longer cooling fan start-up times can be expected when operating.

Thyro-P at temperatures below 10° C. Therefore the adjustment range of upstream protection devices should be at least the 2-fold of the indicated steady current.