68
CONTROL TYPES
Voltage control U
rms
Voltage control U
2
rms
= default setting
Current control I
rms
Current control I
2
rms
Power control P
Without control
PRECISION
U-control: Better than ± 0.5% and ± 1 digit with reference to
the end value.
LIMITATIONS
Voltage limitation U
rms
Current limitaion I
rms
= default setting
Effective power limitation P
Peak current limitation, MOSI operation
Upon reaching one of these limits, the LED ”Limit“ on the
front panel of Thyro-P is on and the relay K2 is activated.
(terminal strip X2, terminals 10/11/12)
Relay K1, K2, K3
Contact load:
AC max:
250V/6A (1500VA)
AC min:
>10VA;
DC max:
300V/0.25A (62.5W)
DC min :
5V/20mA
contactor material: AgCdO
WITH UL APPLICATIONS
AC max:
250V/4A
AMBIENT TEMPERATURE
35°C external cooling (F models)
45°C self air cooling
At higher temperatures it is possible to operate with reduced
type current:
COOLANT
I/I
RATED CURRENT
TEMPERATURE
FORCED COOLING
SELF COOLING
[°C]
(VENTILATOR
TYPES)
-10 bis 25
1.10
1.10
30
1.05
1.10
35
1.00
1.10
40
0.96
1.05
45
0.91
1.00
50
0.87
0.95
55
0.81
0.88
WITH UL APPLICATIONS UP TO +40°C
I/I
Rating
1.2
1.1
1.0
0.9
0.8
0.7
0.6
20
25
30
35
40
45
50
55
60
65
Coolant temperature
Self cooling
Forced cooling