8.SPECIAL REMARKS
8.1INSTALLATION
The installation orientation of
Grounding must be performed according to local regulations of the utility company (grounding screw for protective conductor connection).
8.2 COMMISSIONING
The device must be connected to the mains and the associated load according to the wiring diagrams.
REMARK
It must be observed that with 1P, terminal A1 X1:3 is connected to the U2 on the opposite load side. With 2P it must be observed that terminal A1 X1:3 is connected to the
If the units 1P and 2P are operated at over 600 V and without load at the output side, voltages can occur above input voltage at the connection points U2 and W2. In this case, an additional 690 V damping card is to be used. (Section 12, Accessories and Options)
On delivery, the device is parameterized adjusted to the respective power section. The operating mode TAKT is set. If a different operating mode is desired, then the user must set this using the LBA, PC, etc. Generally, the standard parameters (see menu list) should be reviewed and adjusted to the respective conditions for use by the user (for instance operating mode, control mode, limi- tations, monitoring, times, characteristics, actual value outputs, fault indications, relays, time and date, etc.).
Besides the load, some control signals must be connected as well (refer to chapter 4). The following signals are always required for operation of the device:
Set point | (terminal 10 or 11/or via interfaces) |
RESET | (on ground, on terminal 12, jumper set as standard) |
Regular inhibit | (on ground, on terminal 15, jumper set as standard) |
If the RESET is not connected, then the device is in reset state and is not operating (LED „ON“ shows red light), i.e. no communications is possible via interface. Further details of the RESET are described in chapter 4.4. If the regulator inhibit is not connected, then the device is fully operable, but the power section is only controlled using the values of the minimal limitations (LED „PULSE LOCK“ is on). Further details on the regulator inhibit may be found in the chapter 4.5 of the same name.