2000 VA Output Capability
The 2000 VA Output Capability Option 019 is available on the following ac source model: Agilent 6813B Option 019 AC Power Source (2000VA)
Option 019 increases the output VA capability of the standard Agilent 6813B AC Power Source from 1750 VA to 2000 VA. To achieve the increased output VA capability, the output rms voltage, dc voltage and rms current ratings have increased slightly, to the maximum ratings documented in Table
Specifications for Option 019
Table
Table A-1. Performance Specifications
Parameter |
| Agilent 6813B Option 019 |
Phases: |
| 1 |
Maximum Output Ratings | Power (VA): | 2000 VA |
| dc Power (Watts): | 1500 W |
| rms Voltage: | 308 V |
| dc Voltage: | ± 436 V |
| rms Current (in | 16 A |
| dc Current: | 10 A |
| Repetitive peak Current: | 48 A |
| 48 A | |
| (inrush): |
|
| Crest Factor (current): | 3 @16 A |
|
| (crest factor higher at lower |
|
| currents) |
Output Frequency Range: |
| dc; 45 Hz− 100 Hz |
Programming Accuracy | rms Voltage (45− 100 Hz): | 0.15% + 0.3 V |
(rms detection mode @ 25oC± 5oC), | Frequency: | 0.01% + 10 µ Hz |
± (% of output+offset) | dc Voltage: | 0.5% + 0.3 V |
Measurement Accuracy | rms Voltage (45− 100 Hz): | 0.03% + 100 mV |
(@25oC ± 5oC), ± (% of output + | Frequency: | 0.01% + 0.01 Hz |
offset) | dc Voltage: | 0.03% + 150 mV |
|
Table A-2. Supplemental Characteristics
Parameter | Agilent 6813B (019) |
ac Input Voltage Range (Vac): | 191− 254 Vac |
| (230 Vac nominal) |
Copyright 1999, 2000 AgilentTechnologies, Inc.
2