INSTALLATION TIPS:
1.Use shielded wire for the communication path, and ground one end of the shield to an earth ground.
2.Run intercom wire at least 20" away from AC wiring, fluorescent lights or dimmer switches.
3.Keep intercom cable away from alarm, data, phone, and video cables.
4.Door release wires must be in a separately jacketed cable from the intercom wires. Use two separate cables; one for audio and one for door release.
5.When installing a second master station, wire must be run from the first master station, not from the door station. See diagram on page 2.
6.Do not install master station near light switches, dimmer switches, or other devices that may cause interference with the intercom system.
7.Do not install the master station on the opposite wall from the door station. If the units are too close, acoustical feedback may result.
TROUBLESHOOTING GUIDE:
PROBLEM | POSSIBLE CAUSE | SOLUTION |
|
| (A) Press OFF button on master. If call tone still doesn't come through, |
|
| read solution (B). |
| (A) OFF button on master not pressed. | (B) Make sure jumper is attached to E/- terminals on door station (or |
| proper wires jumpered on | |
No call tone from door to master station. | (B) E/- jumper not attached | connected to E of master. |
|
| Ensure that the jumper at the door station is attached between E and - |
No communication from door station. | E/- jumper not attached | terminals. |
|
| Check power supply. If it's model |
No call tone, no communication. Chirping sound |
| model |
when volume control is turned all the way up. | Wrong voltage on | between |
In a system with |
| Make sure the component module is installed with the bare wire under |
device connected, the external device is activated | the 1 terminal, and the WHITE wire of the | |
every time the TALK button is pressed. | installed incorrectly. | wire. |
In a dual master system, call tone is heard at the |
| Install 1 component module from |
second master when pushing the talk switch on one |
| instructions on Pg. 3. If |
master. | Missing | and capacitor in parallel and install as shown on Pg. 3. |
|
| Ensure that each master has its own power supply. Use any power |
In a dual master system, feedback occurs when |
| supply with output between |
pressing the talk button. | One power supply is used for both masters. | recommends the |
|
| Ensure that the intercom wire is run at least 20" away from any AC |
|
| electrical wire, or crossed at 90 degrees. Intercom wire should be |
|
| shielded, with the drain wire connected to an earth ground at the master |
AC noise when listening to the door station. | Intercom wiring run close to AC wiring. | end. |
|
| Ensure that power wires coming from the |
AC noise when talking to the door station. | Power wires run with communication wires | same jacketed cable with the communication wires run to the door. |