Manufactured (Mobile) Home

Installation . . .

IMPORTANT: Installation must conform to the Manufactured Home Construction and Safety Standards, Title 24 CFR, Part 32-80 or Standard CAN/CSA-Z240 MH.

The dryer can be installed in a manufactured (mobile) home by following these instructions:

1.IMPORTANT: Gas dryers MUST be permanently attached to the floor at the time of installation. Order No. 526P3 Dryer Installation Kit for a manufactured (mobile) home installation. Follow the instructions supplied with the kit.

2.Venting—Dryer MUST be exhausted to the outdoors.

Dryer exhaust MUST NOT terminate under the mobile home.

For proper operation, it is important that the dryer has an ample amount of outside make-up air. The free area of any opening for the introduction of outside air must be at least 163 cm2 (25 in2).

When exhausting the dryer to the outdoors, the dryer can be installed with “0” inch clearance at the sides and rear. Clearance of the duct from combustible construction must be a minimum of 5.1 cm (2 inches).

WARNING

To reduce the risk of fire and combustion gas accumulation, the dryer MUST BE EXHAUSTED TO THE OUTDOORS. Refer to Section on Dryer Exhaust Requirements.

W047

The dryer can be exhausted to the outdoors through the back, left, right or bottom panel. Gas dryers cannot be exhausted out the left side because of the burner housing.

Exhaust duct must be secured to the mobile home structure.

Exhaust ducts MUST NOT be connected with sheet metal screws or fasteners which extend into the duct.

Exhaust duct MUST NOT be connected to any other duct, vent or chimney.

Venting materials are not supplied with the dryer (obtain locally).

WARNING

To reduce the risk of fire, the exhaust duct and weather hood MUST be fabricated of a material that will not support combustion.

Rigid or flexible metal pipe is recommended for a clothes dryer.

W048

504523

27