GAS PIPING
GAS SERVICE INSTALLATION INFORMATION
The size of the gas service pipe is dependant upon many variables, such as tees, lengths, etc. Specific pipe size should be obtained from the gas supplier. Refer to the Gas Pipe Size Chart in this manual for general gas pipe size information.
CAUTION
Gas loop piping must be installed as shown in Illustration, to maintainequalgaspressureforalldryersconnectedtoasingle gas service.
Other gas using appliances should be connected upstream from the loop.
WARNING
(LIQUIFIED PETROLEUM GASES ONLY)
A Gas Pressure Regulator for Liquified Petroleum Gases is not furnished on Gas Heated Clothes Dryers. This regulator is normally furnished by the installer. In accordance with American Gas Association (AGA) standards, a gas pressure regulator, when installed indoors, must be equipped with a vent limiter, or a vent line must be installed from the gas pressure regulator vent to the outdoors.
Page 15