WARNING

The washer-extractor should be connected to an individual branch circuit not shared with lighting or other equipment.

Electrical Specifications WFF65, IWF065, IWF014, CWF065, CWF014

65 liters / 14 pounds

 

 

 

 

 

Boiler Fed/Steam Heat

 

Electric Heat

 

Code

Voltage

Cycle

Phase

Wire

Full Load Amps

 

Recommended Circuit Breaker (US-market)

AWG/mm2

kW Standard Heating Elements

Full Load Amps

 

Recommended Circuit Breaker (US- market)

AWG/mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

US

NON-US

 

 

 

US

 

NON-US

 

N

440-480

50/60

3

3+PE

3

10

10

14/2.5

 

12

15

 

16

14/2.5

P

380-415

50/60

3

3+N+PE

7

15

16

14/2.5

3x2 kW

16

20

 

20

12/4.0

Q

200-240

50/60

3

3+PE

7

15

16

14/2.5

23

30

 

32

10/6.0

 

 

X

200-240

50/60

1/3

2/3+PE

7

15

16

14/2.5

 

N/A

N/A

 

N/A

N/A

 

 

 

 

 

 

 

 

 

Alternative Electric Heat Options

N

440-480

50/60

3

3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

P

380-415

50/60

3

3+N+PE

 

 

 

 

3x1.4 kW

13

15

 

16

14/2.5

Q

200-240

50/60

3

3+PE

 

 

 

 

18

20

 

20

12/4.0

 

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

N

440-480

50/60

3

3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

P

380-415

50/60

3

3+N+PE

 

 

 

 

3x3 kW

21

30

 

32

10/6.0

Q

200-240

50/60

3

3+PE

 

 

 

 

30

40

 

40

8/10.0

 

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

 

 

 

 

 

 

 

Table 2

 

 

 

 

 

 

 