Allied Air Enterprises A93UH, A95UH, 95G1UH Condensate Trap Locations, CONDENSATE ASSEMBLY Figure

Models: 92G1UH 95G1UH A95UH A93UH

1 48
Download 48 pages 41.46 Kb
Page 30
Image 30
CONDENSATE TRAP LOCATIONS

Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available in various lengths; 6 ft. (1.8 m)

-kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69; and 50 ft. (15.2 m) - kit no. 26K70.

CONDENSATE TRAP LOCATIONS

(Unit shown in upflow position with remote trap)

*Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.

Figure 42

(Unit shown in upflow position with remote trap) CAUTION

Do not use copper tubing or existing copper condensate lines for drain line.

CONDENSATE ASSEMBLY

Figure 44

UNIT WITH EVAPORATOR COIL

Figure 45

CONDENSATE TRAP LOCATIONS

(Unit shown in horizontal right hand discharge position)

*Piping from furnace must slope down a minimum

of 1/4” per ft. toward trap.

Figure 43

Page 30 of 48

Issue 1031

506501-01

Page 30
Image 30
Allied Air Enterprises A93UH, A95UH, 95G1UH Condensate Trap Locations, Unit shown in upflow position with remote trap