CONDENSING UNIT SPECIFICATIONS
8
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/
circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
* Up to 24' in equivalent line length
(1) Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2) Maximum Overcurrent Protection Device: MUST use Time Delay Fuses or HACR type Circuit Breaker of the same size as noted.
ASX140181D* / ASX140421D*
ASX140181D* ASX140421D*
Cooling Capacity, BTUH 18, 000 40,000
Compressor
R.L. Amps 9.00 16.7
L. R. Am ps 48.0 79.0
Low Pr es s ure Switc h
Open
Cl ose N/A
N/A 22 PSIG
5 0 PSIG
High Pressure Sw it ch
Open
Cl ose 610 PSI G
420 PSIG 6 10 PSIG
4 20 PSIG
Condens er Fan M otor
Horsepower 1/8 1/6
F.L . Am ps 0. 7 0.9
Liquid Line, Inche s O.D.* 3/8" 3/8"
S uct ion Line, Inch es O.D.* 3 /4" 7/8"
Refr iger ant Char ge 73.0 140.0
P ower S upply 208/ 230-60-1 208/230-60-1
Minimum Ci rcuit Amp acity(1 ) 12 21.8
Ma ximu m Ove rcur r en t D e vic e(2) 20 35
Electr ical Conduit Size
P ower Supply ( Inches ) 1/2 or 3/4 1/ 2 o r 3/4
Approximat e Shipping W eight 146 184