American Aldes LT-20 P E R F O R M A N C E, S P E C I F I C A T I O N S, Options, Hvi Certified

Models: LT-15 LT-20

1 2
Download 2 pages 18.85 Kb
Page 2
Image 2
P E R F O R M A N C E

P E R F O R M A N C E

HVI CERTIFIED

Net Supply airflow in cfm (L/s) against external static pressure

E .S .P .

LT-15[cfm (L/s) ]

LT-20[cfm (L/s) ]

 

0.1" (25 Pa)

 

177 (83)

214 (101)

 

 

 

0.2” (50 Pa)

 

164 (77)

206 (97)

 

 

 

0.3” (75 Pa)

 

156 (73)

193 (91)

 

 

 

0.4” (100 Pa)

 

143 (67)

184 (87)

 

 

 

0.5” (125 Pa)

 

123 (58)

170 (80)

 

 

 

 

 

 

 

 

Max. Sensible Effectiveness

78%

69%

 

 

 

 

 

 

 

 

Test Parameters

67 cfm (32 L/s)

127 cfm (60 L/s)

 

 

 

 

 

 

 

Sensible Effectiveness

 

76%

67%

 

 

 

 

 

 

 

 

 

Sensible Efficiency

 

 

 

 

 

@ 32° F ( 0° C )

 

66%

60%

 

 

 

 

 

 

 

 

 

Sensible Efficiency

 

 

 

 

 

@ -13° F ( -25° C )

 

60%

59%

 

 

 

 

 

 

 

 

 

VAC @ 60HZ

 

120

120

 

 

 

 

 

 

 

 

 

WATTS / High @ .3" w.c.

 

173

182

 

 

 

 

 

 

 

 

 

WATTS / High @ .3" w.c.

 

63

70

 

 

S P E C I F I C A T I O N S

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE: The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS: Each air stream has one centrifugal blower driven by a common PSC motor. 120 VAC, 1.4 Amps.

FILTERS: Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV: Four 10-24 5/8” threaded inserts at corners of case designed to accept four PVC reinforced polyester straps that are sup- plied with the unit.

DEFROST: Damper defrost system; defrosts automatically as the out- door temperature falls.

CASE: Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain

connections 2 - 1/2” (12 mm) OD.

WEIGHT: 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)

CONTROLS: Basic ON/OFF control is maintained with the 3 foot, 120VAC, 3-prong electrical cord providing power to the HRV.

HRV DEFAULTS TO LOW SPEED when plugged in. HIGH SPEED op- tion is accessible by connecting remote, low voltage, 2-wire controls (up to 10) or (up to four 28 884 -20 minute fan timers) to designated terminals inside electrical box of HRV.

STANDARD SPEED SETTING can be increased by manipulating jump- ers in electrical box. OFF (Standby) /LOW or OFF/HIGH speed opera- tion also available by manipulating jumpers.

OFF, LOW and HIGH speeds are all remotely controllable when an op- tional 28 883 Dehumidistat Ventilation Control (DVC) is connected to the HRV’s electrical box.

APPROVALS:

SAFETY: ETL Tested / Certified to UL 1812

 

CSA

 

PERFORMANCE: HVI Tested / Certified to CSA 439-88

BY MATHEWS GRAPHIC DESIGN

CONDENSATE DRAINS

(

28 884

OPTIONS

 

 

 

 

 

 

 

 

20 Minute Fan Timer (3 wire)

 

 

 

 

28 998

Sixty Minute Remote Timer (2 wire)

 

 

 

 

28 883

Dehumidistat Ventilation Control, Remote

 

 

 

 

28 882

Dehumidistat w/ HRV system on/off switch

 

 

All units conform to

Dehumidistat Control, Remote Wall Mount,

 

 

 

 

CSA and UL

 

Horizontal Mounting, Low Voltage white)

 

 

22 026

 

 

Standards

Weatherhoods, 6” (150 mm) c/w 1/4’ (6 mm) screen

 

 

 

 

PROJECT

 

DATE

 

SUBMITTED BY

 

CONTRACTOR

 

 

 

 

 

 

 

 

 

 

 

4537 NORTHGATE COURT SARASOTA, FL 34234-2124, USA Tel: 941 • 351- 3441

Fax: 941 • 351- 3442 www.aldes-us.com e-mail: info@aldes-us.com

WARRANTY

Units carry a 15 year warranty on the heat recovery core and a 2 year replacement parts

warranty.

746HRV-LT-7--00-pm6

RECYCLED PAPER

Page 2
Image 2
American Aldes LT-20, LT-15 P E R F O R M A N C E, S P E C I F I C A T I O N S, Options, Hvi Certified, E .S .P