2.Electrical Service Specifications

ADG-78 II (Gas)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. WHEN ORDERING, SPECIFY EXACT VOLTAGE.

NOTE: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

PHASE

WIRE

APPROX.

MIMIMUM

FUSING

CIRCUIT

DUAL ELEMENT

VOLTAGE

SERVICE

AMP DRAW

WIRE SIZE*

BREAKER

 

 

 

 

 

TIME DELAY

 

120

2

13

#10

20

25

 

 

 

 

 

 

 

208

2

8

#14

12

15

208

3

5

#14

8

15

 

 

 

 

 

 

 

230

2

7

#14

10

15

 

 

 

 

 

 

 

230

3

5

#14

8

15

240

2

7

#14

10

15

 

 

 

 

 

 

 

380-400

3

3

#14

5

15

 

 

 

 

 

 

 

416

3

3

#14

5

15

460

3

3

#14

5

15

* AWG Stranded Wire ... for individual lenghts less than 100 feet.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the back of the dryer, at the upper right hand corner. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.