Top cable entry
| Feed the input cables in | |
conduits (not supplied) through | ||
| ||
| the punched holes. | |
| Run the cables in the side | |
| panel. | |
| Guide the input cables through |
Use cable ties to attach the cable to the slotted plate.
Connect the battery cables Bat+ and Bat÷ and the N cable in the designated areas.
Top cable entry
See how to punch holes in the top cover in section 1: Preparing for top cable entry.
Connecting load to the
|
|
|
the punched holes in the |
bottom plate up to the cable |
landing. |
Use cable ties to attach the |
cables to the slotted plate. |
Use a torx screwdriver to remove the top cable landing covers.
Feed the battery cables |
through the punched holes |
| |
| |
|
|
Connect the input cables (L1, L2, L3), to the cable landings.
Connect the ground cable
|
in the top cover. |
Connect the battery cables |
Bat+ and Bat÷ and the N |
Set the top PDU breaker to the OFF position.
Using a torx screwdriver, remove the four M4 screws from the top plate of PDU. Remove plate.
| |
| using the provided screw (earth |
|
|
| symbol beneath applicable |
| |
L1 | L2 | |
| |
L3 | screw). |
| ||
|
| |||
|
|
|
| |
|
| Reinstall bottom cable landing | 4 | |
|
|
| ||
|
| cover. |
|
3 Battery Cable Landings
The UPS may ONLY be connected to the APC SUVTBXR
Battery Enclosure.
Note
cable in the designated |
areas. |
Connecting Load to the PDU
Preparing to connect the load to the PDU(s)
| Connect the load equipment evenly between the 3 phases to |
| avoid overloading the PDU. The total output capacity of the |
Note | PDU is approximately twice the output capability of the UPS. |
| This means that UPS would be |
| were loaded to their rating. Load status on the individual |
Connect the L1, L2, L3, N to the terminals and tighten the M6 screws firmly. Fasten cables with cable ties.
Attach the ground cable to the ground stud (labeled earth) and fasten with cable tie.
Use a torx screwdriver to reinstall the top plate removed in step 2.
Feed the cable through the hole in the top cover.
Connecting load to the
Set the applicable |
breaker to the OFF |
Bottom cable entry
Use a torx screwdriver to remove top cable landing covers.
Feed the battery cable through the bottom of the UPS. On the outside of the bottom cover, run the cable in conduits (not provided) to the conduit box.
Feed the cables through the conduit box.
phases can be found through the UPS display or through the |
web interface. |
Equipment connected to the
Note output.
For
Note
|
|
| position. |
|
|
| Insert the plug from |
|
| | the load into the |
| | receptacle. Secure | |
|
|
| the plug by turning |
|
|
| it clockwise |
|
|
| approximately 30°. |
|
|
| Set the applicable |
|
|
| breaker to the ON |
|
|
| position to supply |
|
|
| the load. |