10.0 Specifications

9.1 Input

Nominal input voltage: single phase 230 Vac.

Nominal input frequency: 50 or 60 Hz, selected by microprocessor.

9.2 Transfer Characteristics

Frequency limits for on-line operation: ±5% of the nominal 50 or 60 Hz.

Low input voltage limit for on-line operation: 196 Vac.

High input voltage limit for on-line operation: 280 Vac.

9.3 Output Characteristics

Maximum load: 250 VA or 170 W, 400 VA or 250 W, and 600 VA or 400 W for models 250, 400 and 600 respectively.

Nominal output voltage: 225 Vac, ±5%. When verifying UPS on-battery output voltage, use only a true rms responding voltmeter.

Frequency regulation: 50 or 60 Hz, ±3% unless synchronized to the utility.

Waveshape: stepped approximation to sine wave; peak and rms values equiva- lent to the utility.

Protection: electronically overcurrent and short circuit protected, overload shutdown is latched.

9.4 Battery and charger

Battery type: maintenance free lead-acid, sealed and leakproof.

Typical service life: 3-6 years, dependent on number of discharges, temperature.

Low battery signalling: > 2 minute audible tone, interface port signal.

Recharge time: 4 to 5 hours, dependent on load and length of utility outage.

9.5 Surge and noise suppression

Surge energy rating: 320 Joules (one time, 10/1000µs waveform).

Surge current capability: 6500 Amp peak (one time, 8/20µs waveform).

Surge response time: 0 ns (instantaneous) normal mode, <5ns common mode.

Noise filter: full time EMI/RFI suppression, 100 kHz to 10 MHz.

9.6 Operating environment and physical dimensions

Operating environment: 0°C - 40°C (32°F - 104°F), 0 to 95% RH, non condensing.

Size: 6.6" H x 4.7" W x 14.2" D (17 cm x 12 cm x 36 cm).

Weight: 12.1 lb (5.5 kg), 15,4 lb (7.0 kg) and 24.3 lb (11.0 kg) for the UPS models 250, 400 and 600 respectively. Add 2 lb (1 kg) for shipping.