Page 29
8.0 Storing the UPS
8.1 Storage conditions
The UPS should be covered and stored in an upright position, in a cool, dry
location. The UPS should be stored with the battery in a fully charged state. This
means that the UPS should be allowed to charge the battery for at least 6 hours
before the UPS is switched off for storage.
8.2 Extended storage
To achieve expected run time following extended storage, the UPS should be
allowed to refresh the battery for 12 hours once every 6 months in environments
where the ambient temperature is -15°C to +30°C (5°F to 86°F). For extended
storage in environments where the ambient temperature is +30°C to +45°C (86°F
to 113°F), the UPS should be allowed to refresh the battery for 12 hours once every
month.