Troubleshooting

 

Use the table below to solve minor Back-UPS ES installation or operation problems. Consult APC Online Technical Support or call APC

 

 

 

Technical Support for assistance with problems that cannot be resolved using the table below:

 

 

Problem

 

Probable Cause

 

Solution

 

 

 

 

 

 

Back-UPS ES will not turn on.

 

Battery is disconnected and utility power is not available at

 

Connect the battery (see Connect Battery) and ensure power is available at the wall

 

 

 

 

 

 

 

 

the wall outlet.

 

outlet.

 

 

 

 

 

 

 

 

 

No power available at the Surge Protection

 

Surge Protection Only outlets have been overloaded.

 

Reduce the amount of equipment plugged into Surge Protection Only outlets.

 

 

 

Only outlets.

 

 

 

Ensure that the fuse or circuit breaker for the outlet is not tripped, and that the wall

 

 

 

 

 

Utility power not available at the wall outlet.

 

 

 

 

 

 

 

 

switch controlling the outlet (if any) is in the ON position.

 

 

 

Connected equipment loses power.

 

Equipment is connected to the “Surge Protection Only”

 

Ensure that the equipment you want to stay powered during a power failure is

 

 

 

 

outlets.

 

plugged into the “Battery Backup/Surge Protection” outlets and NOT the “Surge

 

 

 

 

 

 

Protection Only” outlets.

 

 

 

 

The Back-UPS ES is overloaded.

 

Make sure that the equipment plugged into the outlets of the unit are not

 

 

 

 

 

 

overloading the capacity of the unit. Try removing some of the equipment and see if

 

 

 

 

 

 

the problem continues.

 

 

 

 

PowerChute Personal Edition software has performed a

 

The Back-UPS ES is operating normally.

 

 

 

 

shutdown due to a power failure.

 

 

 

 

 

 

 

The Back-UPS ES has exhausted its available battery

 

The Back-UPS ES can only operate on battery power for a limited amount of time.

 

 

 

 

power.

 

The unit will eventually turn off when the available battery power has been used.

 

 

 

 

 

 

Allow the unit to recharge for 16 hours before continuing use of the unit.

 

 

 

 

Connected equipment does not accept the step-

 

The output waveform is designed for computers and computer-related equipment. It

 

 

 

 

approximated sine waveform the Back-UPS ES.

 

is not designed for use with motor-type equipment.

 

 

 

 

The Back-UPS ES may require service.

 

Contact APC Technical Support for further troubleshooting.

 

 

 

 

 

 

 

 

 

 

The Power On indicator is lit and the Back-

 

The Back-UPS ES is using battery.

 

The Back-UPS ES is operating normally and using battery power. Once On Battery,

 

 

 

UPS ES is beeping four times every 30

 

 

 

you should save your current work, power down your equipment, and turn the unit

 

 

 

seconds.

 

 

 

OFF. Once normal power is restored, you may turn the unit back ON and power

 

 

 

 

 

 

 

your equipment.

 

 

 

 

 

 

 

 

 

 

 

The Power On indicator flashes once per

 

Battery capacity is low (about 2 minutes of use remaining).

 

The Back-UPS ES is about to shut off due to a low battery charge condition! When

 

 

second and the Back-UPS ES beeps once

 

 

 

the unit beeps once every second, the battery has about 2 minutes of power

 

 

per second at the same time.

 

 

 

remaining. Immediately power down your computer and turn the unit OFF. When

 

 

 

 

 

 

normal power returns, the unit will recharge the battery.

 

 

 

 

 

 

 

 

 

 

Building Wiring Fault indicator is lit.

 

Your building wiring presents a shock hazard. Using the

 

Call a qualified electrician for service.

 

 

 

 

 

Back-UPS with this condition will void the warranty.

 

 

 

 

 

 

 

 

 

 

 

 

 

Inadequate runtime.

 

The battery is not fully charged.

 

Allow the unit to charge by leaving it plugged into the wall at least 16 hours.

 

 

 

 

Battery is near the end of useful life.

 

As a battery ages, the amount of runtime available will decrease. You can replace

 

 

 

 

 

 

the battery by ordering one at www.apc.com. Batteries also age prematurely if the

 

 

 

 

 

 

Back-UPS ES is placed near excessive heat.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications

Item

Specification

BE350R

BE550R

Input

Voltage

120 Vrms

Nominal

 

 

 

 

 

Frequency

50 - 60 Hz (autosensing)

 

 

 

 

 

Brownout Transfer

88 Vrms, typical

 

 

 

 

 

Over-voltage Transfer

139 Vrms, typical

 

 

 

 

Output

UPS Capacity (4 outlets)

350 VA / 200 W

550 VA / 330 W

 

 

 

 

 

Surge Capacity (8 outlets)

12 Amps (including UPS output)

 

 

 

 

 

Voltage

115 Vrms + 8%

 

On Battery

(step-approximated sine wave)

 

 

 

 

 

Frequency - On Battery

50-60 Hz + 1 Hz

 

 

 

 

 

Transfer Time

6 ms typical, 10 ms maximum

 

 

 

 

Protection and Filter

AC Surge Protection

Full time, 375 joules

 

 

 

 

 

Telephone Surge Protection

Single line (2-wire)

 

 

 

 

 

EMI/RFI Filter

Full time

 

 

 

 

 

AC Input

Resettable circuit breaker

 

 

 

 

Battery

Type

Sealed, maintenance-free lead acid

 

 

 

 

 

Average Life

3 - 5 years depending on the number of discharge

 

 

cycles and environmental temperature

 

 

 

 

Physical

Net Weight

9 lbs. (4 kg.)

13 lbs. (6 kg.)

 

 

 

 

 

Dimensions (H x W x D)

3.4" x 10.9" x 7.1"

 

 

(8.6 x 27.7 x 18.0 cm)

 

 

 

 

 

Operating Temperature

+32oF to 104oF (0oC to 40oC)

 

Storage Temperature

+5oF to 113oF (-15oC to 45oC)

 

Operating Relative Humidity

0 to 95% non-condensing

 

 

 

 

 

Operating Elevation

0 to 10,000 ft (0 to 3,000m)

 

 

 

 

Safety/Regulatory

Safety Approvals

UL 1778 listed, cUL certified per

 

 

CSA standard C22.2 No. 107.1, NOM-001

 

 

 

 

 

EMC Compliance

FCC part 68, FCC part 15 Class B

 

 

Notice: This device complies with part 15 of

 

 

the FCC rules. Operation is subject to the

 

 

following two conditions: (1) This device may

 

 

not cause harmful interference, and (2) This

 

 

device must accept any interference received,

 

 

including interference that may cause

 

 

undesired operation.

 

 

 

On the bottom of this equipment is a label that

 

 

contains, among other information, the FCC

 

 

registration number and ringer equivalence

 

 

number (REN) for

this equipment. If

 

 

requested, this information must be provided

 

 

to the telephone company.

 

 

 

 

Order Replacement Battery

Replace with an APC qualified battery. Replacement batteries can be ordered from www.apc.com (valid credit card required). For a Back-UPS ES 350, order RBC35 as directed by APC Technical Support. For a Back-UPS ES 550, order APCRBC110.

Warranty

The standard warranty is 3 years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with APC Technical Support. APC will ship the replacement unit once the defective unit is received by the repair department or cross-ship upon the provision of a valid credit card number. The customer pays for shipping to APC, and APC pays ground freight transportation costs back to the customer.

Service

Please DO NOT RETURN Back-UPS ES to the place of purchase under any circumstances.

1.Consult the Troubleshooting section to eliminate common problems.

2.Verify the battery is connected (see Connect Battery) and that the Circuit Breaker is not tripped (see Troubleshooting section).

If you still have problems or questions, please contact APC via the internet or at one of the phone numbers listed below.

3.Before contacting APC, please be sure to record the date purchased, UPS model, and serial number (on bottom of unit).

4.Be prepared to troubleshoot the problem over the telephone with a Technical Support Representative. If this is not successful, the representative will issue a Return Material Authorization Number (RMA#) and a shipping address.

5.Pack the unit in its original packaging. If the original packaging is not available, ask APC Technical Support about obtaining a new set. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended).

6.Write the RMA# on the outside of the package.

7.Return the unit by insured carrier to the address given to you by APC Technical Support.

APC Contact Information

Online Technical Support

http://support.apc.com

Web Site

www.apc.com

USA/Canada

1.800.800.4272

Mexico

+52.292.0253 / 52.292.0255

Brazil

+0800.12.72.1

Worldwide

+1.401.789.5735

6.50 in.

(165 mm)

Wall Mounting Template

Page 2
Image 2
American Power Conversion 350/550 Troubleshooting, Specifications, Order Replacement Battery Warranty, Service

350/550 specifications

American Power Conversion (APC) has long been a trusted name in the world of power management solutions, and their models 350 and 550 stand out for both reliability and performance. These uninterruptible power supplies (UPS) are designed to provide seamless protection against power interruptions, voltage fluctuations, and surges, making them essential for both home and small business users who rely on electronic equipment.

The APC 350 offers a robust feature set designed for efficiency and user convenience. It has a compact design, making it easy to place in various environments without occupying too much space. One of its standout characteristics is its ability to deliver up to 350 VA output, ensuring that essential equipment remains operational even during outages. The built-in AVR (Automatic Voltage Regulation) technology helps to stabilize voltage fluctuations, ensuring connected devices receive a consistent power supply.

On the other hand, the APC 550 boosts capacity with an output of up to 550 VA, catering to users with greater power needs. This model features multiple outlets that allow for the connection of several devices, providing generous support for workstations, networking equipment, and other critical electronics.

Both models are equipped with an intuitive LCD interface, providing users with real-time information on power conditions, battery status, and load measurements. This user-friendly design allows for easy monitoring, enabling proactive management of power needs.

From a technology standpoint, both the APC 350 and 550 incorporate advanced battery management systems to enhance longevity and performance. They feature sealed lead-acid batteries that are maintenance-free and provide a reliable source of backup power when needed. The automatic self-test feature ensures that the battery is always functioning optimally, alerting users to any potential issues before they become critical.

In terms of energy efficiency, both models come with a green power feature designed to minimize energy consumption, reducing the overall environmental footprint. They are compatible with various operating systems and provide USB connectivity for monitoring and configuring settings with user-friendly software.

Overall, the American Power Conversion 350 and 550 UPS systems seamlessly combine advanced technology with practical features, making them an ideal choice for those looking to safeguard their electronic devices against the unpredictable nature of power supply issues. Whether for personal or professional use, these solutions exemplify reliability and efficiency in power management.