Typical Piping — Redundant Chillers

Typical Piping — Redundant Chillers

CHILLER 1

CHILLER 2

CRACs

Components inside dashed lines are included with the chillers and CRACs. All other items (valves, piping, etc.) are customer-supplied.

Note

Storage tank — optional*

Expansion tank****

Isolation valves

Heat exchanger

Flex connections

Pressure gauges/petcocks

Check valves

Air vent connection port

Chilled water temperature sensor**

Dual pump

Strainer/blow-down valve

Electric heater

Pressure reducing/fill valve

Balance valve/drain plug

Air separator and vent***

Flow switch

*To provide the coldest possible water to the load, install the optional storage tank on the leaving side of the chiller

**Chilled water temperature sensor should be wired to both chillers.

***Install at the highest point in the system.

****When applied in redundant chillers, disconnect the expansion tank and install a single expansion tank in the common header.