42 AIS® 3000 10-40kVA, 400V, Site Preparation and Installation Manual – 990-2258
General Charge Setting
The general charge setting is set to 100% as default.
From the Display it is possible to adjust the charge levels to 75%, 50%, 25%, 10% and 0%.
If the charge limit input is active (J106, pins 7,8) the UPS will reduce the maximum General Charge
effect (100%) to the programmed value.
Charge setting procedure
From the main menu of the display, select Set-up, and press ENTER.
Select System, and press ENTER
Use the arrow keys to get to Gen.Chrg: 100%, and press ENTER.
An arrow will appear to the left of Gen.Chrg. Use the UP arrow on the display to go to the
desired level of charge effect. Select ENTER.
Now, when the charge limit input is active, the UPS will charge to the new setting.
See XR Enclosure, MBP, and Generator Control Wiring for overview of J106.