American Power Conversion APC Silcon 240-320kW 400V Possible Alarms, Alarms and Events, Action

Models: APC Silcon 240-320kW 400V

1 32
Download 32 pages 31.01 Kb
Page 26
Image 26
5.3Possible Alarms

Alarms and Events

5.3Possible Alarms

 

Alarms

Description

Action

 

 

 

1. Peak current limiter active

Peak current limiter activated and

Check for blown fuses in

 

 

UPS switched to bypass operation.

installation

 

 

System overload

 

 

 

 

2. Bypass power supply fault

Fault in redundant PSU for bypass.

Call for assistance

 

 

UPS still 100% able to operate in

 

 

 

all modes.

 

 

 

 

3. Delta current limiter active

Input current limiter activated and

Check for overload.

 

 

UPS switched to bypass operation

If message is repetitive -

 

 

 

call for assistance

 

 

 

4. Faulty fan

Blocked or faulty fan

Remove blocking or replace fan

 

 

 

5. High DC warning

Switching off big output load

If alarm is repeated, reduce load

 

 

 

change

 

 

 

6. High DC shutdown

UPS fault

Call for assistance

 

 

 

7. Off-button activated

Off button or emergency power

 

 

shut down activated

 

 

 

 

8. Synchronization error

UPS unable to synchronize with

Check if phase rotation of mains

 

 

input frequency

input voltage is correct. If OK, call

 

 

 

for assistance

 

 

 

9. Inverter voltage error

Inverter average voltage outside

 

 

limits (normal message during

 

 

 

system start-up/switch-off

 

 

 

 

 

10.

Parallel synchronization

Parallel UPS unable to

Check external parallel cables -

 

error

synchronize

call for assistance

 

 

 

 

11.

Inverter current limiter active

Inverter overload

Reduce UPS output load

 

 

 

 

12.

Overload. Load exceeding

UPS overload

Reduce UPS output load

 

100%

 

 

 

 

 

 

13.

Second power supply fault

UPS fault

Call for assistance

 

 

(only systems > 160kW)

 

 

 

 

 

14.

Internal power supply fault

UPS fault. Only bypass operation

Call for assistance

 

 

possible

 

 

 

 

 

15.

Battery MCCB is off

Battery MCCB/fuse not closed or

Close MCCB / insert new fuse. If

 

 

released

released again -

 

 

 

call for assistance.

 

 

 

 

16.

**Q004 off**

Output switch position for UPS in

 

 

parallel

 

 

 

 

 

17.

**Q003 off**

External bypass switch position

 

 

 

 

18.

**Q002 off**

UPS output switch position

 

 

 

 

19.

**Q001 off**

UPS input switch position

 

 

 

 

20.

High temperature of isolation

Temperature of isolation input/

Check fan, check for airflow

 

transformer

output transformer, too high

obstructions, check for overload

 

 

 

21. High temperature of main static

Temperature of static input switch,

Check fan, check for airflow

 

switch

too high

obstructions, check for overload

 

 

 

 

22.

High temperature of bypass

Temperature of static bypass

Check fan, check for airflow

 

static switch

switch, too high

obstructions, check for overload

 

 

 

 

990-4037

26

User Guide APC Silcon 240-320kW 400V UPS

Page 26
Image 26
American Power Conversion APC Silcon 240-320kW 400V manual Possible Alarms, Alarms and Events, Description, Action