Installation

Prior to installing the power supply enclosure utility line voltage must be routed to the enclosure. Local, state, federal and/or National Electric Code (NEC) regulations regarding location, permits and electrical wiring must be adhered to.

Do not operate the power supply where the temperature and humidity are outside the specified limits. See Specifications in this manual. Position the enclosure ensuring adequate airflow around the unit for proper ventilation.

Specifications

Model Number

Input
Output
Battery Type

CP150E48

87-132 VAC

46-52 VDC

The use of an APC

 

176-264 VAC

150 W

battery is recommended.

 

50/60 Hz

 

Contact APC or your

 

 

dealer for details.

 

 

 

Environmental Specifications

Operating Temperature

-40º F to 131º F (-40º C to 55º C)

 

 

Operating Humidity

0 to 100% noncondensing within enclosure

Max Operating Elevation

10,000 ft (3,000 m)

 

 

Max Storage Elevation

50,000 ft (15,000 m)

 

 

Recommended Storage Temperature

41º F to 95º F (5º C to 35º C)

Physical Specifications

Characteristic

Specification

Height X Width X Depth

17” x 17” x 10” excluding the bracket

 

(12” including the bracket)

 

(43 x 43x 26 cm excluding the bracket

 

(31 cm including the bracket)

 

 

Weight

 

Enclosure without a battery

18 lbs (8.2 kg)

Enclosure with a battery

100 lbs (45.4 kg)

 

 