Page 23
Image 23

MX28B600-48V

a 50 A. circuit breaker located in circuit breaker Position 1. The interface card provides fuseholders for eight fuses, labeled “F1” through “F8”, which can be used for small -48V DC loads. The maximum fuse size that should be used is 10A.

5.7.3 Load Connections

5.7.3.1 Circuit Breakers

Connections for -48V DC loads require standard two-hole lugs for #10 screws on 5/8” centers and are located directly above the corresponding circuit breaker. The load returns connect to the respective return bus located just above and rearward of the breaker connection points. The upper tier is seen in Figure 4.7-1.The return buses provide a total of 40 sets of threaded #10-32 holes on 5/8” centers and four sets of threaded ¼”-20 holes on ¾” centers for connection of two- hole lugs on load return wires.

5.7.3.2 Optional GMT Fuses

Connections to the GMT fuses are made at terminal block connectors labeled “F1” through “F8” that are located on the interface card mounted in the top left side of the unit. Each connector has two positions, labeled “-48V” and “RTN”, for connection of the -48V DC load and load return wires.

5.8Battery Temperature Probe Installation

The optional temperature probe is used to monitor the battery string temperature. To get the most representative temperature measurement, the probe should be placed in contact with a battery cell that is centrally located. The probe should be placed directly in contact with the cell (not the frame surrounding the cell). Generally, the cell cover can be used; be careful not to allow the probe body to touch the terminals.

1) Plug the connector end of the temperature probe into J5 the control unit backplane card.

2)Route the cable as required to position the probe on the selected battery cell

3)Remove the adhesive protection strip from the probe body and press the adhesive side of the probe on the battery cell cover.

J5

5.9Power-Up and Checkout

Before initiating power-up and checkout, ensure that the following conditions exist:

1)Make sure that the external circuit breaker protecting the cables from the battery to the power plant is turned OFF (the battery cables should be connected to the power plant, but the battery should not be connected).

2)Make sure that all load circuit breakers are turned OFF (including the one feeding the GMT fuses if the unit has the GMT fuse option).

3)Verify that all rectifiers have been installed.

19

Page 23
Image 23
American Power Conversion MX28B600 manual Load Connections Circuit Breakers, Battery Temperature Probe Installation

MX28B600 specifications

The American Power Conversion (APC) MX28B600 is a top-of-the-line uninterruptible power supply (UPS) designed to provide reliable power protection for a variety of applications. Known for its robust features and advanced technologies, the MX28B600 is an ideal solution for small to medium-sized data centers, telecommunications systems, and other critical IT infrastructure.

One of the standout features of the MX28B600 is its high capacity, which allows it to support a wide range of devices while accommodating future growth. With a power rating of 28 kVA, it can effectively handle multiple servers and network equipment without compromising performance. This capacity ensures business continuity even during power outages, surges, or fluctuations.

The MX28B600 utilizes advanced Double Conversion Online technology, which provides consistent and clean power to connected equipment. This technology ensures that the output voltage is tightly regulated, protecting sensitive electronics from damage and improving overall reliability. Additionally, the UPS features a wide input voltage range, allowing it to function effectively even in unstable power environments.

Another critical characteristic of the MX28B600 is its modular design, which provides flexibility for customization and scalability. Users can easily add or remove modules based on their evolving power requirements, making it a cost-effective solution over time. This modularity also simplifies maintenance and reduces downtime, ensuring that businesses can remain operational without interruptions.

The APC MX28B600 incorporates a user-friendly interface that makes monitoring and managing power needs straightforward. Its LCD display provides real-time information on battery status, output power, and alerts, allowing users to make informed decisions quickly. Additionally, the UPS is equipped with Remote Manager capabilities, enabling remote monitoring and management from any location, which is especially beneficial for IT administrators responsible for multiple sites.

Designed with energy efficiency in mind, the MX28B600 meets stringent environmental standards. Its Eco mode and Intelligent Battery Management system optimize battery life, reduce energy costs, and lower carbon emissions, contributing to a more sustainable operation.

In conclusion, the APC MX28B600 is an exceptional choice for businesses looking for reliable and efficient power protection. With its high capacity, advanced technologies, modular design, and energy-efficient operation, it is poised to meet the demands of modern organizations while ensuring continuous uptime and protecting critical equipment.