USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-Test

Every 14 days

Every 7 days(168 hours),

Set the interval at which the

 

(336 hours)

14 days (336 hours)

UPS will execute a self-test.

 

 

On Startup Only,

 

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters to

Uniquely identify the UPS, (i.e.

 

 

define the UPS

server name or location) for

 

 

 

network management purposes.

 

 

 

 

Date of Last Battery

Manufacture Date

Date of

Reset this date when you replace

Replacement

 

Battery Replacement

the battery modules.

 

 

mm/dd/yy

 

 

 

 

 

Minimum Capacity

0 percent

0, 15, 25, 35, 50, 60, 75,

Following a low-battery

Before Return from

 

90 percent

shutdown, the battery modules

Shutdown

 

 

will be charged to the specified

 

 

 

percentage before powering

 

 

 

connected equipment.

 

 

 

 

Alarm Delay After

5 second delay

5 or 30 second delay

Mute ongoing alarms or disable

Line Failure

 

At Low Battery

all alarms permanently.

 

 

Never

 

 

 

 

 

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,

Set the interval between the time

 

 

720, 960 seconds

when the UPS receives a

 

 

 

shutdown command and the

 

 

 

actual shutdown.

 

 

 

 

Duration of

2 minutes

2, 5, 7, 10, 12, 15, 18,

The low battery warning beeps

Low Battery Warning.

PowerChute

20 minutes

are continuous when two

 

 

minutes of run time remain.

 

software provides

 

 

automatic,

 

Change the warning interval

 

unattended

 

default to a higher setting if the

 

shutdown when

 

operating system requires a

 

approximately 2

 

longer interval for shutdown.

 

minutes of battery

 

 

 

operated runtime

 

 

 

remains.

 

 

 

 

 

 

Synchronized Turn-on

0 seconds

0, 20, 60, 120, 240, 480,

The UPS will wait the specified

Delay

 

720, 960 seconds

time after the return of utility

 

 

 

power before turn-on (to avoid

 

 

 

branch circuit overload).

 

 

 

 

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

 

output voltage

+20%

will pass to connected

 

setting

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

 

 

8

 