9
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT
ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION FACTORY
DEFAULT
USER SELECTABLE
CHOICES DESCRIPTION
Low Bypass Point -30% of output
voltage setting
-15%, -20%, -25%, -30% Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage XLJ models:
200 VAC
XLT models:
208 VAC
XLI models:
230 VAC
XLTW models:
220 V
XLJ models:
200 VAC
XLT models:
200, 208, 220, 230,
240 VAC
XLI models:
200, 208, 220, 230,
240 VAC
XLT/XLTW models:
200, 208, 220, 230,
240 VAC
Allows the user to select the
UPS output voltage while
online.
Output Frequency Automatic
50 ± 3 Hz or
60 ± 3 Hz
50 ± 3 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of
Battery Packs
1 Number of Connected
Internal Battery Packs,
(two modules per pack)
Defines the number of internal
and external connected battery
packs for proper run time
prediction.
CONNECTING THE EPO (EMERGENCY POWER OFF) OPTION The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to National and local electrical codes when wiring the EPO. The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers. The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC standard). EPO switch