NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE

 

FUNCTION

 

 

FACTORY

 

 

USER SELECTABLE

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

DEFAULT

 

 

CHOICES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Battery

 

2 minutes

 

2, 5, 7, 10 minutes

 

The UPS will beep when 2 minutes of

 

Warning

 

PowerChute

 

(Times are approxi-

 

battery runtime remains.

 

 

 

 

 

 

 

 

 

 

 

 

Business Edition

 

mate.)

 

Change the low battery warning inter-

 

 

 

 

software provides

 

 

 

 

val setting to the time that the operat-

 

 

 

 

automatic, unat-

 

 

 

 

ing system or system software requires

 

 

 

 

tended shutdown

 

 

 

 

to safely shut down.

 

 

 

 

when approxi-

 

 

 

 

 

 

 

 

 

 

mately 2 minutes

 

 

 

 

 

 

 

 

 

 

of battery oper-

 

 

 

 

 

 

 

 

 

 

ated runtime re-

 

 

 

 

 

 

 

 

 

 

mains.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized

 

0 seconds

 

0, 15, 45, 75 seconds

 

Specify the time the UPS will wait

 

Turn-on Delay

 

 

 

 

 

 

 

after the return of utility power before

 

 

 

 

 

 

 

 

 

 

turn-on (to avoid branch circuit over-

 

 

 

 

 

 

 

 

 

 

load).

 

 

 

 

 

 

 

 

 

High Transfer

 

110/120 V model:

 

110/120 V model:

 

Set the high transfer point higher to

 

Point

 

127 Vac

127, 130, 133, 136

 

 

avoid unnecessary battery usage when

 

 

 

 

 

 

 

Vac

 

the utility voltage is usually high and

 

 

 

 

230 V model:

 

230 V model:

 

the connected equipment is specified

 

 

 

 

 

 

to operate with input voltages this

 

 

 

 

253 Vac

253, 257, 261, 265

 

 

 

 

 

 

 

 

high.

 

 

 

 

 

 

 

Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Transfer Point

 

110/120 V model:

 

110/120 V model:

 

Set the low transfer point lower when

 

 

 

 

106 Vac

97, 100, 103, 106

 

 

the utility voltage is usually low and

 

 

 

 

 

 

 

Vac

 

the connected equipment is specified

 

 

 

 

230 V model:

 

230 V model:

 

to operate with input voltages this low.

 

 

 

 

 

 

 

 

 

 

 

 

208 Vac

196, 200, 204, 208

 

 

 

 

 

 

 

 

 

 

 

Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Page 10
Image 10
American Power Conversion VA 1000, VA1500, Vac 110, Vac 230, Vac 120 user manual 110/120 V model