TROUBLESHOOTING GUIDE

 

 

 

 

 

Symptom

Possible Cause

 

Action

 

 

 

 

 

 

Display does not come

Thermostat is not being

 

Check if the thermostat is mounted and latched on the

 

on.

powered.

 

wallplate—mount and latch the thermostat on the

 

 

 

 

wallplate.

 

 

 

 

Check if the circuit breaker is tripped—reset the circuit

 

 

 

 

breaker.

 

 

 

 

Check if the fuse is blown—replace the fuse.

 

 

 

 

Check if the system switch at the equipment is in the Off

 

 

 

position—set to the On position.

 

 

 

 

Check wiring between thermostat and HVAC equipment —

 

 

 

replace any broken wires.

 

 

 

 

If 24 Vac is present, proceed with troubleshooting.

 

 

 

 

 

 

Temperature setting

The upper or lower temperature

 

Check that the temperature setpoints are:

 

does not change

limits were reached.

 

Heating: 55 to 85°F (13 to 29°C)

 

(Example: cannot set the

 

 

Cooling: 65 to 99°F (18 to 37°C).

 

heating higher or the

 

 

 

 

cooling lower).

 

 

 

 

 

 

 

 

 

 

 

(continued)

 

 

 