The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Must terminate a maximum of 6 in. (15cm) above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 ft. (9.14m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve (see Figures 3 & 19).

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 in. (15cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Shall terminate a maximum of 6 in. (15cm) above a floor drain or external to the building. In cold climates, it is recommended that the discharge line be terminated at an adequate drain inside the building.

Shall not have any valve between the relief valve and tank.

The temperature-pressure relief valve must be manually operated at least once a year, (see Figure 17). Caution should be taken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot.

FIGURE 17

If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.

T&P Valve and Pipe Insulation (if supplied)

Remove insulation for T&P valve and pipe connections from carton.

FIGURE 18

Fit pipe insulation over the incoming cold water line and the hot water line. Make sure that the insulation is against the top cover of the heater. Fit T&P valve insulation over valve. Make sure that the insulation does not interfere with the lever of the T&P valve.

Secure all insulation using tape.

20

www.americanwaterheater.com

Page 20
Image 20
American Water Heater 316888-004 warranty Valve and Pipe Insulation if supplied

316888-004 specifications

The American Water Heater 316888-004 is a reliable and efficient choice for homeowners seeking a dependable and effective water heating solution. Designed with a focus on performance and convenience, this water heater provides an impressive array of features that meet the demands of modern living.

One of the standout characteristics of the 316888-004 is its efficient heating technology. The unit employs advanced heating elements that ensure rapid heating of water, reducing wait times for hot water availability. This feature is particularly beneficial for households with high hot water demands, such as those with multiple bathrooms or numerous appliances requiring hot water simultaneously. By delivering hot water quickly, this model enhances user satisfaction and improves overall household efficiency.

In terms of design, the American Water Heater 316888-004 boasts a compact structure, which makes it suitable for various installation environments, including tight spaces. Its durable construction is complemented by high-quality materials, ensuring longevity and reduced maintenance costs. This model is built to withstand the rigors of daily use, providing peace of mind to homeowners regarding its reliability and durability.

Safety is another important aspect of the 316888-004. The unit is equipped with multiple safety features, including a temperature and pressure relief valve, which helps prevent overheating and excessive pressure buildup. Additionally, it accommodates users' needs for energy efficiency, making it an environmentally friendly option. The device is designed to minimize energy consumption, which not only lowers utility bills but also contributes to reducing the household's overall carbon footprint.

Moreover, the 316888-004 is user-friendly, featuring a simple control interface that makes adjusting temperature settings easy. This accessibility allows users to customize their water heating experience according to their personal preferences.

In conclusion, the American Water Heater 316888-004 stands out as a top choice in its category. With its efficient heating technology, durable construction, focus on safety, energy efficiency, and user-friendly features, it meets the diverse needs of contemporary households. For anyone seeking a reliable, high-performance water heater, the 316888-004 is undoubtedly a smart investment, ensuring consistent hot water availability for years to come.