American Water Heater BCG3-100T250-6NOX Two Temperature - One Heater High Temperature Storage

Models: BCG3-85T390-6NOX BCG3-100T250-6NOX Commercial Gas, Glass-Lined, Tank-Type Water Heater BCG3-80T150-6NOX

1 32
Download 32 pages 8.68 Kb
Page 13
Image 13
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE

TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE

WITH RECIRCULATION OF SANITIZING LOOP

NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE RINSE OPERATION AND OPEN (OFF) WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY.

NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD BE SET AT 185°F (85°C).

NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK.

* TEMPERED WATER LOOP, IF USED, CONNECT TO POINT “A”.

**PIPE RELIEF VALVE TO OPEN DRAIN.

INSTALL IN ACCORDANCE WITH LOCAL CODES.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE

PROVIDED.

WITH RECIRCULATION OF SANITIZING LOOP DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARYTO OBTAIN ADEQUATE BOOSTER OUTPUT, ADDANANTI- SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.

13

Page 13
Image 13
American Water Heater BCG3-100T250-6NOX, BCG3-80T150-6NOX Two Temperature - One Heater High Temperature Storage, Danger