Quick Start Guide

AXR-IRSM+Swivel-Mount Remote IR Receiver

Overview

The AXR-IRSM+ (FIG. 1) is a remote IR receiver for use with both AMX Axcess/NetLinx Central Controllers and operates via the AXlink bus to remotely control AXlink devices. The AXR-IRSM+ is in a swivel-mount enclosure for wall or ceiling installations. The AXR-IRSM+ (FG454-01) works with AMX 38 kHz or 455 kHz IR transmitters.

Note: The AXD-IR+ wallmount version is also available for US-style single-gang enclosure installations.

Circuit board

assembly Housing

Swivel mount base

IR Data

LED IR Sensor

IR Data LED

IR

Sensor

 

 

 

 

 

 

IR SNSR

 

 

 

 

 

 

 

IR SNSR

 

 

 

 

 

 

38/455

 

 

 

 

 

 

 

38/455

 

 

 

 

 

 

kHz

 

 

 

 

 

 

 

kHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting for 38 kHz

 

Setting for 455 kHz

FIG. 3 Receive frequency jumper settings

Note: The unit will not operate with one set of pins configured for 38 kHz and the other set of pins configured for 455 kHz.

To receive 455 kHz (default setting), position both jumpers on pins 1 and 2 (away from the edge of the circuit boards).

To receive 38 kHz, position both jumpers on pins 2 and 3 (near the edge of the circuit boards).

Setting the AXlink Device Number

1.Locate the 8-position Device DIP switch (FIG. 2).

2.Set the device address according to the DIP switch values shown below.

Switch

1

2

3

4

5

6

7

8

Value 1 2 4 8 16 32 64 128

The device number is set by the total value of DIP switch positions that are ON (down). The Axcess software program in your system typically uses device numbers 128 through 255 for the panels.

As an example, the DIP switch in FIG. 4 defines device number 129 (1+128=129).

FIG. 1 AXR-IRSM+ swivel-mount IR receiver

AXR-IRSM+ Specifications

Dimensions (HWD):

3.30" x 2.00" x 2.6" (83.80 mm x 50.80 mm x 66.00 mm)

 

 

Receive Frequencies:

38 / 455 kHz (user-selectable)

 

 

Enclosure

Neutral off-white metal enclosure (FG454-01)

 

 

Mounting:

May be used without the wall bracket for flush mounting.

 

Comes with full set of mounting screws and wall anchors.

 

 

Weight:

5.6 oz (174 grams)

 

 

Power Consumption:

35 mA

 

 

Wiring and Installation

Set the receive frequency, AXlink device number and IR validation level before installing the AXR-IRSM+. To access the jumper pins or switches on the circuit board assembly, separate the housing from the swivel base, as shown in FIG. 1.

FIG. 2 illustrates the location of key components on the AXR-IRSM+ circuit board.

IR Validation

Jumper Pins

8-position

AXlink Device

AXlink

DIP Switch

Connector

Receive Frequency

Jumper Pins

FIG. 2 Location of key components on the AXR-IRSM+circuit board

Setting the Receive Frequency

FIG. 4 Example Device DIP Switch set to 129

Note: If you later change the device number, remove and reconnect the AXlink connector to enter the new device number into memory.

Sensor IR Validation Level

The IR validation level is set on the receiving device (such as an AXC-RCVI).

Setting the IR Validation Level

An IR transmitter must send repetitions of data for the receiver to accept it as valid data. In some installations, a light wall color or other physical condition may interfere with the sensor's or receiver's ability to sense the transmitted signal. The signal may reflect or bounce and become distorted. The receivers can be set to use either two or three repetitions of sequential signals to validate and accept the signal data.

Perform the following steps to set the receiver's IR validation level.

1.Locate the IR Validation jumper pins (J1) (FIG. 5) on the circuit board (FIG. 2).

 

2

3

 

 

 

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting for 2 validations

Setting for 3 validations

FIG. 5 IR validation jumper pin settings

2.Position the IR validation jumper (FIG. 5) to select the number of valid IR data repetitions to be accepted:

Position the jumper at 2 to have the unit validate 2 sequential signals.

Position the jumper at 3 to have the unit validate 3 sequential signals.

Wiring the IR Sensors and Receivers

Use the set of jumper pins on the corner of the circuit board to set the receive frequency. FIG. 3 illustrates the configuration of the jumpers.

The AXR-IRSM+ uses a 4-pin AXlink connector for power and data. If the distance between the sensor and Central Controller exceeds power