Installation Sheet
RDM-ZC50 Zero Cross Module 6000 W
The
Mounting points
Line in (hot) | |
Load out | connections |
Zero cross relay
FIG. 1
RDM-ZC50 UL and C-UL Ratings
Suggested Switched Loads
•Incandescent
•Electronic transformers
•HID ballast
•Fluorescent ballast
Specifications
•Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
•
•Use 75°C (167°F) copper conductors only
•Torque terminals to 16
•Max. wire size: 6 AWG; 14 AWG min.
•Wire stripping length: 0.35" (9 mm)
•Weight: 1.0 lb. (0.45 kg)
•BTU/hr: 400
•Control current: 45 mA @ 12 VDC
Caution: Pre-Installation Notes
Connecting the RDM-ZC50 to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
3
1 (+)
NOTE: The
the
FIG. 2
Lighting Application Drawing
All neutrals are common to the Neutral block in the enclosure. Provide a separate neutral for each load.
Neutral
Line in (HOT) |
|
| Load |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Fluorescent Lighting |
| Ballast |
| Load |
Circuit breaker | Neutral |
panel |
|
| Neutral |
| Load |
| Neon lights |
| |
FIG. 3 |
|
•All Class 1 wiring must be connected to proper terminals.
•All control wiring must be connected to proper terminals.
•Disconnect power while installing or connecting the unit.
•Keep top and bottom air vents clear at all times.
•Test loads for shorts before connecting.
•Run all
•Each dimming circuit must have a separate neutral connection.
•All electrical ratings are for continuous duty.
•AC lighting loads only.
•For indoor use only.
•This module may require extra power from the AXlink connection or an external power supply connected to the control card.