NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

High Transfer

120V Models

120V Models

To avoid unnecessary battery usage, set

Point

132 VAC

138, 135, 129 VAC

the high transfer point higher if the

 

230V Models

230V Models

utility voltage is chronically high and

 

253 VAC

264, 271, 280 VAC

the connected equipment is known to

 

 

 

work under this condition.

 

 

 

 

Low Transfer

120V Models

120V Models

Set the low transfer point lower if the

Point

103 VAC

97, 100, 106 VAC

utility voltage is chronically low and

 

230V Models

230V Models

the connected equipment can tolerate

 

196 VAC

188, 204, 208 VAC

this condition.

 

 

 

 

16

Page 18
Image 18
APC 2200VA, 3000VA user manual High Transfer