PROBLEM AND POSSIBLE
CAUSE
SOLUTION
THERE IS NO UTILITY POWER AND THE UPS HAS BEEN TURNED OFF
120V/230V Models: When the UPS is off and there is no utility power, use the cold start feature to apply power to the connected equipment from the UPS battery.
Cold start is not a normal condi- tion.
Press and hold the button, (for about 3 seconds). The unit will beep, the LED lights will flash, and the unit will beep a second time. Release the ON button during the second beep. This will supply imme- diate power to the UPS and the connected equipment. Make sure con- nected equipment is switched to ON.
UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
UPS input circuit breaker tripped.
Very high, low, or distorted line voltage. Inexpensive fuel powered generators can distort the voltage.
Reduce the load on the UPS by unplugging equipment and resetting the circuit breaker (on the back of UPS) by pressing the plunger in.
Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display (see below). If acceptable to the connected equipment, reduce the UPS sensitivity.
BATTERY CHARGE AND BATTERY LOAD LEDS FLASH SIMULTANEOUSLY
The internal temperature of the UPS has exceeded the allowable threshold for safe operation.
Check that the room temperature is within the specified limits for opera- tion.
Check that the UPS is properly installed allowing for adequate ventila- tion.
Allow the UPS to cool down. Restart the UPS. If the problem continues contact APC at, www.apc.com/supoport.
DIAGNOSTIC UTILITY VOLTAGE FEATURE
Utility Voltage
The UPS has a diagnostic feature that displays the utility voltage. Plug the UPS into the normal utility power.
Press and hold the button to view the utility voltage bar graph dis-
play. After a few seconds the
Refer to the figure at left for the voltage reading (values are not listed on the UPS).
The display indicates the voltage is between the displayed value on the list and the next higher value.
Three LEDs light, indicating utility voltage within the normal range.
If no LEDs are lit and the UPS is plugged into a working utility power outlet, the line voltage is extremely low.
If all five LEDs are lit, the line voltage is extremely high and should be checked by an electrician.
The UPS starts a
12