Alarms

The microprocessor controller shall activate a visible and audible alarm in the following occurrences:

Cool Fail

Rack inlet temperature violation

Rack inlet temperature sensor fault

Air filter clogged

Air filter run hours exceeded

Filter DP sensor failure

Supply air sensor fault

Return air sensor fault

Supply air high temperature violation

Return air high temperature violation

Fan fault

Fan run hours exceeded

Water detection fault

Condensate pump fault

Condensate run hours exceeded

Humidifier water conductivity high violation

Humidifier fault tolerance exceeded

Humidifier low water

Humidifier excessive output reduction

Humidifier drain fault

Humidifier cylinder full

Humidifier replace cylinder

Humidifier RS485 communication fault

Humidifier run hours violation

Humidity high/low violation

Supply humidity sensor fault

Return humidity sensor fault

Heater fault

Heater run hours exceeded

Heater interlock shutdown

Group communication fault

Internal communication fault

A-link isolation relay fault

External communication fault

Input contact fault

Invalid supply setpoint

Idle mode active

Chilled Water Only Alarms

Coil fluid valve actuator fault

Fluid flow fault

Entering fluid temperature high violation

Entering fluid temperature sensor fault

Leaving fluid temperature sensor fault

Power source failure

Fluid calibration

Air-cooled Only Alarms

High discharge pressure

Low suction pressure

High suction pressure

Compressor drive failure

Compressor drive warning

Compressor run hours violation

Compressor drive RS485 communication fault

Excessive compressor cycling

Air flow decreased while compressor off

Suction pressure sensor failure

Discharge pressure sensor failure

High pressure switch active

Fan speed decreased to avoid high pressure (event only)

Compressor speed decreased to avoid high pressure (event only)

Compressor high pressure

Oil return pump active