P.SELECTABLE TOP OR BOTTOM PIPING (AIR-COOLED ONLY)

1. Pipe connections: The unit is equipped with field connection from either top or bottom of the unit. Unit connections shall be made internal to the unit.

2. Pipe adapters: The unit shall include 1-in Rotolock to sweat adapters and associated Teflon seals.

Q.FLOW METER

1. Flow meter shall be factory piped inside the unit and connected to microprocessor controls to provide water flow rate through the unit. The microprocessor controller shall also use this information to provide total unit capacity out of the unit while in operation.

2. Flow meter shall be stainless steel construction turbine type meter, compatible with glycol/ water solutions up to 50%, with accuracy of 1.5% or better on range 5-50 GPM.

R.CABLE WATER DETECTOR (OPTIONAL)

1. The optional leak detection sensing cable shall be shipped loose with the unit. If water or other

conductive liquids contact the cable anywhere along its length, the main controller visually and audibly annunciates the leak.

2. The optional detector shall be provided with a 6.1 m (20 ft) of cable. Cable may be cascaded up to 24.4 m (80 ft).

S.BRIDGE POWER CABLE TROUGH

1. An overhead power distribution bridge, that sits between adjacent NetShelter racks and allows for removal of the unit without disrupting the overhead power cabling, is available as an accessory.

2. Cable trough shall be constructed of 1.5 mm (16 gauge) cold rolled steel with a black powder coat finish.

T.BRIDGE DATA PARTITION

1. An overhead cable distribution, that sits between adjacent Netshelter racks and allows for removal of the unit without disrupting overhead cabling, is available as an accessory.

2. Data partition shall be constructed of 1.5 mm (16 gauge) cold rolled steel with a black powder coat finish.

U.COOLING FLUIDS

Chilled Water and solutions of propylene or ethylene glycol up to 50% may be used. Solutions of brine or other aqueous salt are NOT permitted.

V. FREEZE PROTECTION

Per ASHRAE Handbook Fundamentals 2001 21.5, a maximum of 30% ethylene glycol and 35% propylene glycol are needed for freeze protection. Please consult ASHRAE handbook for more details.

InRow RP Technical Data Manual

43

Page 47
Image 47
APC ACRP101, ACRP501, ACRP502, ACRP500, ACRP102, ACRP100 manual Selectable TOP or Bottom Piping AIR-COOLED only

ACRP502, ACRP500, ACRP501, ACRP102, ACRP101 specifications

The APC ACRP series, consisting of models ACRP100, ACRP101, ACRP102, ACRP501, and ACRP500, represents a significant innovation in power distribution and protection. These compact, reliable, and efficient solutions are designed specifically for critical applications in data centers, industrial environments, and commercial facilities.

The ACRP100 is the entry-level model, providing essential features for basic power monitoring and control. It incorporates advanced metering capabilities, enabling users to monitor voltage, current, and power consumption in real-time. The ACRP100's user-friendly interface allows for easy navigation, making it an ideal choice for small to medium-sized installations that require fundamental power management.

Stepping up, the ACRP101 enhances functionality with added remote monitoring capabilities. This model introduces smart connectivity features, allowing users to access critical data from anywhere through a secure mobile application or web-based platform. With its ability to integrate seamlessly with other APC systems, the ACRP101 is tailored for environments seeking improved operational visibility and proactive maintenance.

The ACRP102 takes a further leap by integrating advanced predictive analytics. This model uses machine learning algorithms to analyze data trends, predicting potential failures before they occur. By minimizing downtime and optimizing maintenance schedules, the ACRP102 becomes a vital tool for organizations focused on reliability and efficiency.

In the higher-end range, the ACRP501 offers robust power management features, including enhanced surge protection and redundancy capabilities. This model is ideal for mission-critical operations where every second counts. It supports a wide range of input voltages and can manage multiple power sources concurrently, ensuring uninterrupted power supply in fluctuating conditions.

Lastly, the ACRP500 combines all the leading features of the series, focusing on scalability and flexibility. This model is engineered to adapt to evolving infrastructure needs, supporting modular configurations that can grow with the organization. Its extensive reporting functions and customizable dashboards provide clear insights into power usage and performance metrics, empowering facility managers to make informed decisions.

In summary, the APC ACRP series provides a comprehensive suite of solutions for power management, tailored to meet diverse operational needs. From basic monitoring with the ACRP100 to the predictive capabilities of the ACRP102 and the advanced functionalities of the ACRP500, these models collectively offer enhanced reliability, efficiency, and scalability while ensuring optimal protection for critical applications.