Module Information - Continued
Model PNETR5 - In applications where the network data transmission rate is high and cable lengths are long, insertion loss introduced by in-line devices is a major consideration. At the 100 Mbp/s data transmission rate there is a small insertion loss introduced by the PNETR5. Use Table 1 below to approximate the insertion loss introduced by the PNETR5 based on your installed cable type. The ISO/IEC 8802-3 standard specifies a maximum UTP cable length of 150 meters per segment at 10 and 100 Mbp/s. For Thinnet, maximum cable length is 185 meters (607 ft.).
Model PNETR6 - Applications where the network data transmission rate is high and cable lengths are long, an insertion loss is introduced by in-line devices. At 250 Mbp/s there is a small insertion loss introduced by the PNETR6. Use Table 1 below to approximate the insertion loss based on the installed cable type. The ISO/ IEC 8802-3 standard specifies a 150 meter maximum UTP cable length per segment at 250 Mbp/s.
Table 1
EIA/TIA 568 Category or | Frequency | Attenuation | Equivalent Cable |
Cable Type | (MHz) | (db/100m) | Length (m) |
| | | |
3 | 10 | 9.8 | 1.0 (3.28 ft) |
| | | |
| 16 | 13.1 | 1.10 (3.5 ft) |
| | | |
| 16* | 0.1* | 1.0 (3.28 ft.) |
| | | |
4 | 10 | 7.2 | 1.4 (4.5 ft) |
| | | |
| 16 | 8.9 | 1.6 (5.2 ft) |
| | | |
5 | 10 | 6.6 | 1.5 (4.9 ft) |
| | | |
| 16 | 8.2 | 1.7 (5.6 ft) |
| | | |
5 | 100 | 22 | 12.5 (41 ft) |
| | | |
5e | 100* | 2.2* | 10 (32.8 ft.) |
| | | |
6 | 250* | 5.8* | 17.1 (56.1 ft.) |
Note: Entries marked with an asterisk ( * ) are only valid for PNETR6.
Model PVR (Digital Cable Protection)
The PVR module provides digital cable protection for video/cable/modem equipment against surges and spikes caused by lightning and electrostatic discharge (ESD). It is compatible with cable television (CATV), a digital satellite system (DSS), television, video cassette recorder (VCR), cable modem and TV antenna equipment. It is also compatible with many DSS units that have operating voltages below 26 volts DC. The PVR is recognized by Underwriter’s Laboratories (UL® ) as a secondary protector.
Item | Specification |
EN 50083-4, Attenuation and Return Loss | <6 dB from 54-550 MHz and <8 dB 550-1002 MHz |
| |
Ingress Susceptance EIA 23 | (-26) dBmV |
| |
Radiated Emissions | 15 dBmV 360 degree |
| |
Frequency Range | 1 MHz though 2.0 GHz |
| |
Insertion Loss | 0 dB to 3.0 dB over rated frequency range |
| |
Agency Approvals | UL 497B, FCC 47 CFR 15, CLB-47 CFR Part 15 Subpart C |
| |
Model PTEL2R (Analog Telephone Protection)
The PTEL2R module protects analog devices, including telephones, ADSL, ISDN2, voice mail, automated answering systems, fax machines and modems, from damage caused by lightning-generated electrical transients. Each PTEL2R module protects up to 2 lines.
Item | | Specification |
Lines Protected | Pins 3 & 4 / 5 & 6 on RJ-45 connector; accepts RJ-45/RJ-11 plugs |
| |
Mode of Protection | Metallic (Tip - Ring) and longitudinal (Tip + Ring - Ground) |
| |
Peak Voltage | ± 2,000 Volts, 1.2/50 µs test waveform |
| | |
Peak Current | 150 | Amps, 8/ 20 µs test waveform |
| | |
Breakover (turn on) Voltage | 270 | Volts peak nominal between tip and ring |
| |
Overload Protection | Solid-state, self-resetting fuse |
| |
Response Time | <1 ns |
| |
Agency Approvals | UL 497A recognized |
Warning: Disconnect module wires before removing module. Do not put fingers or objects inside the chassis.
Module Information - Continued
Model P232R (RS232 Protection)
The P232R module is used for RS232 communications (RS232 multiports, asynchronous multiplexers, asynchronous printer spoolers) using unshielded, twisted-pair wiring with RJ-45 connectors. It protects up to four ports per unit.
Item | Specification |
Lines Protected | Pins 1 - 8 on RJ-45 connector |
| |
Mode of Protection | Between send/receive pairs and any signal line to ground |
| |
Peak Voltage | ± 2,000 Volts, 1.2/50 µs test waveform |
| |
Peak Current | 150 Amps, 8/ 20 µs test waveform |
| |
Breakover (turn on) Voltage | 19 Volts nominal between send/receive pairs |
| |
Response Time | <1 ns |
| |
Model PDIGTR (Digital Telephone Protection)
The PDIGTR module is only designed to be used in T1, CSU, DSU, ISDN, DDS and Digital Leased Line telecommunication equipment, and TNV-1 or SELV circuits. Insertion loss introduced by in-line devices is a major consideration.
Item | Specification |
Lines Protected | Pins 1 - 8 on RJ-45 connector |
Mode of Protection | Between send/receive pairs and any signal line to ground |
Peak Voltage | ± 2,000 Volts, 1.2/50 µs test waveform |
Peak Current | 100A (maximum with 10X 1000 µs waveform |
Operating Current | 150 mA maximum |
Breakover (turn on) Voltage | Metallic (line-to-line): 60Vdc nominal |
Response Time | <1 ns |
Regulatory Approval / Classification | UL 497A recognized, FCC |
Service
If the device arrived damaged, notify the carrier immediately.
If the device requires service, do not return it to the dealer. The following steps should be taken:
1.Go to http://www.apc.com/support/.
2.Have the model number, serial number and date of purchase available. Be prepared to troubleshoot the problem with an APC Technical Support representative. If this is not successful, APC will issue a Return Merchandise Authorization (RMA) number and a shipping address.
Limited Lifetime Warranty
APC warrants its products to be free from defects in materials and workmanship under normal use and service for the lifetime of the original purchaser. Its obligation under this warranty is limited to repairing or replacing, at its sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from APC or an APC Service Center. Product must be returned to APC or an APC Service Center with transportation charges pre-paid and must be accompanied by a brief description of the problem and proof of date/place of purchase. This warranty applies only to the original purchaser.
Customer Service / Technical Support
For information please call the APC Customer Service Center at:
American Power Conversion | 1-401-789-5735 or 1-800-800-4APC (4272) |
132 Fairgrounds Road | http://www.apc.com/support or |
West Kingston, RI 01892 USA | esupport@apcc.com |
Federal Communications Commission (FCC) Notice
This equipment contains an FCC compliant RJ-45 modular jack. It is designed to be connected to the telephone network or premises wiring using compatible modular plugs and cabling, which comply with the requirements of FCC Part 68 rules. The Ringer Equivalence Number (REN) is used to determine the number of devices that may be connected to the telephone line. An excessive REN may cause the equipment to not ring in response to an incoming call. In most areas, the sum of the RENs of all equipment on a line should not exceed five (5).
In the unlikely event that this equipment causes harm to the telephone network, the telephone company can temporarily disconnect your service. The telephone company will try to warn you in advance of any such disconnection, but if advance notice isn’t practical, it may disconnect the service first and notify you as soon as possible afterwards. In the event such a disconnection is deemed necessary, you will be advised of your right to file a complaint with the FCC.
From time to time, the telephone company may make changes in its facilities, equipment, or operations that could affect the operation of connected equipment. If this occurs, the telephone company is required to provide you with advance notice so you can make the modifications necessary to maintain uninterrupted service. This product is not serviceable by the user.
Entire contents copyright 2006 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.
APC and the APC logo are registered trademarks of American Power Conversion Corporation. All other trademarks are the property of their respective owners.
990-1383B 05/2006