Function

Factory Default

Options

Description

 

 

 

 

Turn Off Delay

90 sec

Set the value in

The amount of time that the Switched Outlet

 

 

seconds

Groups will wait between receiving the command

 

 

 

to turn off and the actual shut down.

 

 

 

 

Reboot Duration

8 sec

Set the value in

The amount of time that the Switched Outlet

 

 

seconds

Groups must remain off before it will restart.

 

 

 

 

Minimum Return

0 sec

Set the value in

The amount of battery runtime that must be

Time

 

seconds

available before the Switched Outlet Groups will

 

 

 

turn on again after a shutdown.

 

 

 

 

Load Shed On

Disabled

• Shutdown with

When the unit switches to battery power, the UPS

Battery

 

Delay

can disconnect power to the Switched Outlet

 

 

• Shutdown

Groups to save runtime.

 

 

immediately

Configure this delay time, use the LOAD SHED

 

 

• Turn off

 

 

immediately

TIME WHEN ON BATTERY setting.

Turn off with delay

Disabled

Load Shed Time

Disabled

Set the value in

The amount of time the outlets will function on

when On Battery

 

seconds

battery power before they will turn off.

 

 

 

 

Load Shed On

Disabled

• Shutdown with

Configure this time using the LOAD SHED

Runtime

 

delay

RUNTIME REMAINING setting.

Shutdown immediately

Turn off immediately

Turn off with delay

Disabled

Load Shed On

Disabled

Set the value in

When the remaining runtime reaches this level,

Runtime

 

seconds

the Switched Outlet Groups will turn off.

Remaining

 

 

 

 

 

 

 

Load Shed on

Disabled

• Disabled

In the event of an overload (greater than 105%

Overload

 

• Enabled

output), the Switched Outlet Groups will

 

 

 

immediately turn off to conserve power for

 

 

 

critical loads. The Switched Outlet Groups will

 

 

 

only turn on again with a manual command.

Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC).

NMC IP Address Mode

NMC Default Gateway

12

Smart-UPS X 2000/2200/3000 VA

Page 14
Image 14
APC SMX2200RMHV2U, SMX3000RMJ2U, SMX3000RMLV2UNC, SMX3000RMHV2UNC, SMX2000RMLV2U Network Management Card Settings