General Settings
Configure these settings at any time, using the display interface, APC PowerChute® software, or a network management card.
Function | Factory Default | Options | Description | |
|
|
|
| |
High Transfer | Low Voltage |
|
| |
Point |
|
|
| |
100 V: 108 Vac |
| |||
|
|
|
| |
| 110 V: 116 Vac | To avoid unnecessary battery usage, set the | ||
| 120 | V: 127 Vac | transfer point higher if the utility voltage is | |
|
|
|
| chronically high and the connected |
| 127 | V: 134 Vac | ||
|
|
|
| equipment is known to work under this |
| High Voltage |
| ||
|
| condition. The POWER QUALITY setting will | ||
|
|
|
| |
| 200 | V: 216 Vac | ||
| automatically change this setting. | |||
| 208 | V: 220 Vac | Note: Use the Advanced Menus to configure | |
|
|
|
| this setting. |
| 220 | V: 242 Vac | ||
|
|
|
|
|
| 230 | V: 253 Vac |
| |
|
|
|
|
|
| 240 | V: 264 Vac |
| |
|
|
|
| |
Low Transfer | Low Voltage |
|
| |
Point |
|
|
| |
100 V: 92 Vac |
| |||
|
|
|
| |
| 110 V: 98 Vac | Set the transfer point lower if the utility | ||
|
|
|
| |
| 120 V: 106 Vac | |||
| voltage is chronically low and the connected | |||
|
|
|
| |
| 127 V: 112 Vac | |||
| equipment can tolerate this condition.The | |||
| High Voltage |
| POWER QUALITY setting will automatically | |
|
|
| change this setting. | |
| 200 V: 184 Vac | |||
|
|
|
| Note: Use the Advanced Menus to configure |
| 208 V: 184 Vac | |||
| this setting. | |||
|
|
|
| |
| 220 V: 198 Vac | |||
|
| |||
|
|
|
| |
| 230 V: 207 Vac |
| ||
|
|
|
| |
| 240 V: 216 Vac |
|
Green Mode If the UPS input voltage is between the high transfer point and the lower transfer point, the unit will operate in green mode. Configure this setting using the Advanced menus.
Transfer | Normal | • Normal | Select the level of sensitivity to power |
|
Sensitivity |
| • Reduced | events that the UPS will tolerate. | |
|
| • Low | • Normal: The UPS will go on battery power | |
|
|
| more often to provide the cleanest power | |
|
|
| supply to the connected equipment. | |
|
|
| • Reduced: The UPS will tolerate some | |
|
|
| fluctuations in power. | |
|
|
| • Low: The UPS will tolerate more | |
|
|
| fluctuations in power and will go on | |
|
|
| battery power less often. | |
|
|
| If the connected load is sensitive to power | |
|
|
| disturbances, set the sensitivity to Normal | |
|
|
| using the advanced Configuration menu. | |
|
|
|
|
|
Low Runtime | 150 sec | Set the value in | The UPS will emit an audible alarm when | |
Warning |
| seconds | the remaining runtime has reached this level. | |
|
|
|
| |
Date of Last | Date set at factory | Reset this date when the battery module is replaced. | ||
Battery |
|
|
|
|
Replacement |
|
|
|
|
9 |