Operating Instructions
Front View
|
| Status | Select | Status Select | To UPS B | AC Source | To UPS A | To Server | ||
|
|
| Level |
|
| B | A |
|
|
|
|
| Function |
|
|
|
|
|
|
| |
R | I + |
|
|
|
|
|
|
|
| |
T | N 2 |
|
|
|
|
|
|
|
|
|
N | 4 |
|
|
|
| Bright | Source selected |
|
| |
| EPO |
|
|
|
| Dim | Source OK, but not selected |
| ||
Emergency |
|
|
|
|
| |||||
Power Off |
|
|
|
| Off | Source not OK | Redundant Switch |
| ||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
|
|
| Note: |
|
|
|
|
|
|
|
Only the Factory Default settings shown below should be used. Check that these are the current settings for your unit.
Additional setting are for future upgrades.
Function | Factory | User Selectable Choices | Description | ||
| Default | LED Bright | LED Dim | LED Off |
|
Source A Sensitivity | Reduced | Normal | Reduced | Low | Sets transfer sensitivity to line |
|
|
|
|
| conditions |
Source B Sensitivity | Reduced | Normal | Reduced | Low | Sets transfer sensitivity to line |
|
|
|
|
| conditions |
Source Preference | Source A | Source A | Source B | None | Selects the preferred AC source |
Source A Xfer Voltage | Medium | Narrow | Medium | Wide | Sets the transfer voltage window |
Source B Xfer Voltage | Medium | Narrow | Medium | Wide | Sets the transfer voltage window |
Emergency Power Off
The UPS may be switched off by a remotely operated Emergency Power Off (EPO) control. Such a configuration is common in computer rooms and laboratories where, for safety reasons, power to the loads must be disconnected. To connect Redundant Switch and its attached
Cautions
The EPO interface is a Safety Extra Low Voltage (SELV) circuit and may be connected only to other SELV circuits.
The EPO interface is designed to monitor circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. Connection of the EPO interface to any circuit other than a closure type circuit may cause damage to the Redundant Switch.
Front Panel User Programming
User programmable settings are accessible using controls located on the Redundant Switch front panel.
Function Select LED Indicator
The three green Function Select LEDs indicate which user programmable parameter is selected for status display or modification. Use the left Select button to cycle through the five user configurable items listed above.
Function Status LED Indicator
The green Function Status LED indicates the state of the selected user programmable function. Use the right Select button to cycle among the choices.
AC Source LED Indicator
The green
Source Sensitivity and Transfer Voltage
Source sensitivity and transfer voltage can be changed using the front panel to adjust for power quality. However, only the factory default settings shown above should be used.