2. Connect additional Extended Run Cabinets
Connect each additonal extended run cabinet to the previously installed cabinet. The Symmetra LX supports a maximum of seven cabinets.
2.1Remove the screw and UPS battery connector panel from the previously installed cabinet.
2.2Connect the power cable from the new cabinet into the battery
connector of the previous cabinet.
2.3Set the dial of the new cabinet to a number that is one higher than that of the previous cabinet
.
2.4Connect the communications cable from the communications connector of the new cabinet
to that of the previous cabinet
.
3. Verify Connection
• To verify the connection, the UPS must be on. For further information, see the Symmetra LX
Note • Messages regarding battery quantity may be visible on the UPS PowerView display.
3.1Check that the green status light on the rear of each cabinet will light.
3.2Check that the front display shows the correct dial number.
3.3Refer to the status menu on the UPS PowerView display (see the Symmetra LX Operations Guide) to verify that the number of battery modules matches the total number of battery modules installed in the UPS and all extended run cabinets. Also, verify there are no bad battery modules present.
Troubleshooting
It is assumed that the Symmetra LX is powered and functioning during these startup procedures. If the problem persists, call technical support. Visit the the APC website at http://www.apc.com/support for contact information.
Problem | Possible Cause | Solution | |
|
|
| |
The green status LED (rear | There is no battery power | Check that the battery cable | |
of frame), and the front | present at the frame. | and battery modules are | |
| properly installed. | ||
display (front of frame) do |
| ||
not light after the | The communication cable is | Check that the | |
communication cable is | |||
not installed | communication cable is | ||
installed. | |||
| properly installed. | ||
|
| ||
|
|
| |
| The display cable is not | See the Extended Run | |
The green status LED | connected. | Cabinet Physical Installation | |
| Guide for proper cable | ||
lights, but the front display |
| ||
| connection instruction. | ||
does not show the frame |
| ||
number. | There is a potential hardware | Call technical support. | |
| failure. |
| |
|
|
| |
The front display | More than one frame is set | Check that frame numbers | |
continuously flashes on | with the same frame number. | are not duplicated on the | |
and off. |
| communication card(s). | |
|
|
| |
| The “E_O” frame error code | Check that the battery cable | |
| may indicate that the battery | is properly installed. If the | |
| cable is not installed. | error code continues to flash, | |
|
| call technical support. | |
|
|
| |
An “XR frame failure” is | The “E_7” frame error code | Check that the | |
may indicate that the | communication cable is | ||
reported. The front display | |||
communication cable is not | properly installed. If the error | ||
flashes an error code. | |||
installed | code continues, call | ||
| |||
|
| technical support. | |
|
|
| |
| All other LED error codes | Call technical support and | |
| could indicate a potential | report the error code. | |
| hardware failure. |
| |
|
|
| |
The front display | A failed battery module has | Replace the battery module. | |
alternately flashes the | been detected in the location | To obtain a replacement | |
frame number and either | displayed. | battery, see the APC | |
“Lx” , “Cx”, or “Rx”. |
| website. | |
|
|
| |
| One or more battery module | Check that the disconnect | |
| disconnect switches are off | switch on all modules is | |
The number of battery | (opened). | closed | |
|
| ||
modules reported is | Battery modules are not | Check that all battery | |
inaccurate. | installed correctly. | modules are properly | |
|
| installed in the extended run | |
|
| frame(s). | |
|
|
|