SAFETY NOTEIn the United Kingdom,
ionisationsmoke detectorsare
subjectto the requirements of
the RadioactiveSubstances
Act 1993 and to the Ionising
Radiations Regulations1999
made under the provisions
of the Health and Safetyat
Work Act 1974.
Thedetectors,independently
tested by the National
RadiologicalProtection
Board(NRPB), conform toall
the requirementsspecified
in the ‘Recommendationsfor
ionisation smokedetectors in
implementationof radiation
standards’ publishedby the
NuclearEnergyAgency ofthe
Organisation for Economic
Co-operation and
Development (OECD)1977.
Thereis nolimitto the number
of ionisation smokedetectors
which may be installedin
any fire protectionsystem
within the UK. See
Certificate ofApproval No.
TA1 of 1999 issuesby the
HSE for further details.
Storage regulationsdepend
on local standardsand the
legislation,but, in the UK, the
numberof ionisationsmoke
detectorsin any buildingor
premisesshall beless than
500. See Certificateof
ApprovalNo. TA3 of1999
issuedby the HSE forfurther
details.
At the end of their
recommended workinglife
of ten years, ionisation
smoke detectorsshould be
returned to Apollofor safe
disposal or disposedof in an
otherwise locallyapproved
and environmentallysafe
manner. Pleasesee "A Guide
to the Care, Maintenance
and Servicing ofApollo
Products", PP2055.
Guidance on storagecan be
given by Apollo Fire
Detectors and fulldetails
can be requestedfrom:
Radioactive Substances
Regulation Function
Environment Agency
Rio House, WatersideDrive
Aztec West, Almondsbury,
Bristol, BS32 4UD
Outsidethe UK, pleasecontact
therelevantnational agency.
For wind speeds up to 1m/s
(200ft/min) the change in
analogue value will not
exceed 5 counts.
Continuous operation in
wind speeds greater than
2m/s (400ft/min) is not
recommended. However,
wind speeds up to 10m/s
(2000ft/min)can be tolerated
for short periods and will
not under any conditions
increase the probability of
false alarms.
TECHNICAL DATA
XP95 Ionisation
DetectorPart No 55000-500/
520/560
Base Part No 45681-210
Specificationsare typical
and given at 23°Cand 50%
relative humidityunless
otherwisestated.
Detector Type:
Point type smoke detector for
fire detection and fire alarm
systems for buildings
Detection Principle:
Ionisation Chamber
Chamber Configuration:
Twin compensating
chambers using one single
sided ionising radiation
source
Radioactive Isotope:
Americium 241
Activity:
33.3kBq, 0.9µCi
Sampling Frequency:
Continuous
Sensitivity:
Nominal threshold y value of
0.7 to EN54–7:2000
technical data
Supply Wiring:
Two wire supply, polarity
insensitive
Terminal Functions:
L1&L2 supply in and out
connections(polarity
insensitive)
+R remote indicator
positive connection
(internal 2.2kΩ
resistance to supply
+ve)
-R remote indicator
negativeconnection
(internal 2.2kΩ
resistance to supply
- ve)
Supply Voltage:
17 to 28 Volts dc
Modulation Voltage at
Detector:
5 to 9 Volts peak to peak
Quiescent Current:
280µA average, 500µA peak
Power-up Surge Current:
1mA
Duration of Power-up Surge
Current:
0.3 seconds
Maximum Power-up Time:
4secondsforcommunications
(measured fromapplicationof
power and protocol)
10 seconds to exceed 10
counts 15 seconds for stable
clean air value
Clean Air Analogue Value:
25±7 counts
Alarm Level 55 Counts:
EN54 y value of 0.7
Alarm Indicator:
Redlight emittingdiode(LED)
Alarm LED Current:
2mA
Remote LED Current:
4mA at 5V (measured across
remote load)
Type Code:
(210 43) 011 00
Storage Temperature:
-30°C to +80°C
Operating Temperature:
-20°C to +70°C
Guaranteed Temperature
Range:
(No condensation or icing)
-20°C to +60°C
Humidity:
(No condensation or icing)
0% to95% relative humidity
Wind Speed:
10m/s maximum
Atmospheric Pressure:
Automatic compensation by
dual chambers to maintain
sensitivity up to a height of
2000m above sea level
Vibration, Impact & Shock:
To EN54–7:2000
Electro-magnetic
Compatibility:
See page 21 for full details
IP Rating:
23D
Approvals & Regulatory
Compliance:
See page 21 for full details
Dimensions:(diameterxheight)
Detector: 100mm x 42mm
Detector in Base:
100mm x 50mm
Weights:
Detector: 105g
Detector in Base: 161g
Materials:
Detector Housing: White
polycarbonate V-0 rated to
UL 94
Terminals: Nickel plated
stainless steel