Model 1510 Media Air Cleaner Installation Instructions
WARNING
CAUTION
1.High voltage may cause serious injury from electrical shock. Disconnect power to the furnace/air handler before starting installation.
2.Sharp edges may cause injury from cuts. Use care when cutting and handling sheet metal.
1.To prevent component failure, do not install the air cleaner on the warm air supply or in an area where the temperature may exceed 140°F. This may include areas above heat exchangers in downflow furnaces or above exhaust flues in lowboy furnace cold air returns.
2.Installation must be done by a qualified heating and air conditioning professional. Read instructions thoroughly before beginning installation.
3.Do not install air cleaner downstream of a UV light. UV lamps will cause degradation of the filtering media.
SPECIFICATIONS
Model | 1510 |
|
|
Airflow Capacity | up to 3000 CFM maximum |
|
|
Replacement Media | Model 510 or 513 with SelfSeal™ |
|
|
Max. Equipment Weight | Cabinet will support 400 lb. static load |
|
|
Air Cleaner Operating Environment | Temperature: 0°F – 140°F. Humidity: 0 – 90% |
|
|
DIMENSIONS
B
without door
C
A
D
E
with door
F
G H
TABLE 1 – Dimensions (inches)
Model | A | B | C | D | E | F | G | H |
1510 | 31 | |||||||
|
|
|
|
|
|
|
|
|