TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE

PROBLEM

POSSIBLE CAUSE(S)

SOLUTION(S)

 

 

 

 

ON/OFF switch not in ON position

Turn switch ON.

 

 

 

Light does not

Air cleaner not plugged in

Plug in air cleaner.

come on at all after

Insufficient current to activate

Wrap blower common wire around relay bracket more – see

90 seconds

Model 51 relay

Figure 14 on page 7 for wire wrapping method.

 

 

 

 

Furnace/air handler not running

Turn blower on by making a heat call or turning Fan ON.

 

 

 

 

 

Ensure components are dry.

 

 

 

 

 

Excessive humidity - run cooling to lower humidity levels.

 

 

 

 

Over current or arcing detected

Ensure that all 9 ionizer wires are held at both ends.

 

 

Light flashes on

Look for foreign object contacting ionizer wires or buss bar.

 

 

 

 

Door not fully installed - ensure door is latched into top and

then off quickly

 

 

bottom retainer.

 

 

 

 

 

 

Insufficient current to sustain Model

Wrap blower common wire around relay bracket more – see

 

51 relay

Figure 14 on page 7 for wire wrapping method.

 

 

 

 

Loose connection in outlet junction box

Check wire nuts, screw terminals and crimped connectors for

 

or at furnace/air handler EAC terminal

loose wires. Use only fully insulated crimped connectors.

 

 

 

Light stays on after

Outlet in which air cleaner is plugged

See Step 1 in Wiring and Start Up section – page 6.

blower stops running

is continuously live

 

 

 

 

 

Outlet in which air cleaner is plugged

See Step 1 in Wiring and Start Up section – page 6.

 

is continuously live

 

 

 

 

 

 

Large crack/hole in media

Replace media.

 

 

 

 

Poor connection between media

Remove ground strip and reinstall as shown in Figure 11

 

ground strip and media

on page 5.

 

 

 

Produces an

Poor contact between control

Push in control electrode so it fully seats in the ionizer frame –

ozone smell

electrode and ground contact

see Figure 16 on page 10.

 

 

With the inner assembly installed in the outer housing, bend up

 

Ground contacts not touching

ground contacts (2-media ground contacts, 1-control electrode

 

door liner

ground contact) so they are at least 3/4” higher than the top of

 

 

the inner housing. Refer to Figure 11 and Figure 16.

 

 

 

 

Media ground contacts not

Remove ground contacts and reinstall as shown in Figure 11

 

fully installed

on page 5.

 

 

 

 

Large crack/hole in media

Replace media.

 

 

 

 

Poor connection between media

Remove ground strip and reinstall as shown in Figure 11

 

ground strip and media

on page 5.

 

 

 

Makes a buzzing

Poor contact between control

Push in control electrode so it fully seats in the ionizer frame.

electrode and ground contact

 

sound or causes TV

 

 

 

With the inner assembly installed in the outer housing, bend up

interference

 

Ground contacts not touching

ground contacts (2-media ground contacts, 1-control electrode

 

 

door liner

ground contact) so they are at least 3/4” higher than the top of

 

 

the inner housing. Refer to Figure 11 and Figure 16.

 

 

 

 

Media ground contacts not

Remove ground contacts and reinstall as shown in Figure 11

 

fully installed

on page 5.

 

 

 