INSTALLATION INSTRUCTIONS (continued)
Figure 5 | 3/4" x 1" Reducing Coupling |
|
|
| Dispersion Tube |
|
|
| Steam Hose |
|
|
|
| |
| 1" Copper Pipe |
| |
|
|
| |
Steam Hose |
|
| |
| Humidifier |
|
|
|
|
| |
Humidifier |
|
|
|
Do not mount humidifier in a location where ambient temperature | Figure 6 – Clearances |
| |
exceeds 120ºF or where freezing temperatures may occur.. |
|
|
|
Mount humidifier in a location that allows access for servicing, and |
|
| 16" for |
clearance to remove front panel for replacing the canister and side |
|
| Steam |
|
| Hose | |
panel for access to the electrical components during installation.. |
| FRONT VIEW |
|
See Figure 6 for minimum clearances around humidifier.. |
|
| |
|
|
| |
The humidifier should be mounted as close to the dispersion |
|
|
|
tube as possible.. Table 3 shows how capacity is reduced as the |
| 16" for | 30" for |
distance between the humidifier and dispersion tube increases.. If | 4" | Electrical | Service |
the humidifier is mounted on the duct directly below the dispersion | Access | Access | |
|
|
| |
tube, allow space for a bend in the steam hose.. |
|
|
|
The humidifier can be mounted to a wood surface, or to sheet metal |
|
| |
ductwork if it is structurally stable.. Do not mount humidifier to fiber |
|
|
|
duct board.. |
|
|
|
The humidifier must be mounted to a vertical surface and must be |
| 16" | SIDE VIEW |
|
| ||
mounted level in the upright position.. |
| for Drain |
|
Do not mount humidifier near sources of electromagnetic emissions |
|
|
|
such as power distribution transformers.. |
|
|
|
|
|
|
ADHC (Automatic Digital humidifier Control) Model 62
The ADHC must be mounted in the return air duct at least 6” upstream of any fresh air intake ducts or sources of moisture (steam dispersion tube if it is in the return..) Follow instructions provided with the control..