To Test Thermostat
WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.
CAUTION: Do not switch system to cool if the temperature is below 50°F (10°C). This can damage the air conditioning system and cause personal injury.
Operation
Setting or Changing the Setpoint Temperature
1. Press either the | >or>button. |
The display will show the current
temperature setpoint. | > | > |
|
|
Changing Fahrenheit (F) to Celsius (C)
The thermostat is preset to display the temperature in degrees Fahrenheit. You may change the display readout to Celsius if desired.
1.Move the manual switch marked “F” (Fahrenheit) and “C” (Celsius) located at the top center of the circuit board to the desired setting.
2.Press RESET button located lust below the LCD display to register the change.
Wiring Diagrams
The following is just a sample of the most common types of HVAC systems. Refer to your systems installation manual for wiring information.
HEAT/COOL | HEAT ONLY |
SINGLE TRANSFORMER | SINGLE TRANSFORMER |
Limited Warranty
Your Research Products Corporation Aprilaire® Thermostat unit is expressly warranted for two (2) years from date of installation to be free from defects in materials and workmanship.
Research Products Corporation’s exclusive obligation under this warranty shall be to supply, without charge, a replacement for any thermostat which is found to be defective within a two (2) year period and which is returned,
1. Place the | COOL OFF HEAT | |
into the COOL position |
|
|
2. Press the>button until the |
|
|
|
| |
temperature setting is at least |
|
|
3 degrees below the room temperature. |
|
|
The air conditioning system should |
|
|
turn on within a few seconds. |
|
|
> | > | COOL OFF HEAT FAN: AUTO - ON |
2. Press either the >or> button to adjust the temperature setting either up or down.
The display will change to show the temperature in your desired temperature scale. To return the thermostat to its original setting, repeat steps 1 and 2 above.
TROUBLESHOOTING
|
|
|
|
|
| |||||
|
|
|
|
|
| jumper |
| |||
|
|
|
|
|
|
|
| RH |
| T |
Transformer |
|
|
|
| H | |||||
|
|
|
|
|
|
|
|
|
| E |
| Hot |
|
|
|
|
|
| RC | R | |
120 VAC |
| 24 VAC |
|
|
|
| ||||
|
|
|
|
|
| Heating |
| W | M | |
|
|
|
|
|
| Control |
| |||
|
|
|
|
|
|
|
|
|
| O |
|
|
|
|
|
| Cooling |
| Y | S | |
|
|
|
|
|
| Control |
|
|
| T |
|
|
|
|
|
|
|
|
|
| A |
|
|
|
|
|
| Fan |
| G | T | |
|
|
|
|
|
| Control |
| |||
|
|
|
|
|
|
|
|
|
Factory- Installed
jumper
|
| RH | T | |
Transformer | H | |||
| ||||
Hot |
| RC | E | |
120 VAC | 24 VAC |
| R | |
| Heating | W | M | |
| Control | |||
|
| O | ||
|
|
| ||
|
| Y | S | |
|
| T | ||
|
|
| ||
| Fan | G | A | |
| Control | T | ||
|
|
together with the date of installation, no later than thirty (30) days after said two (2) year period by you to either your original supplier or to Research Products Corporation, Madison, Wisconsin 53701.
THIS WARRANTY SHALL NOT OBLIGATE RESEARCH PRODUCTS CORPO- RATION FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE THERMOSTAT ITSELF.
NOTE: When in the COOL mode (or HEAT and COOL for single stage heat pumps), once the thermostat turns off, a built in
The display will return to the room temperature display five seconds after the last input and the new setpoint will be saved.
Symptom | Remedy |
Thermostat does not turn | Check Wiring |
on system | (see INSTALLATION). |
| Check fuse. Replace with 2 amp |
HEAT ONLY |
|
COOL ONLY | |
SINGLE TRANSFORMER | |
| SINGLE TRANSFORMER |
NOTE: Remove factory installed jumper
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID TWO YEAR PERIOD. RESEARCH PRODUCTS CORPORATION’S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES
fuse if fuse has opened. |
RH
T
3.Put the
4.Put the
COOL OFF HEAT
COOL OFF HEAT
Thermostat turns on and | Increase Temperature Differential |
off too frequently. | (see DIFFERENTIAL). |
|
|
Display is blank, flashing | Replace batteries. |
or constant “LO BAT”. |
|
|
|
|
|
|
|
Transformer
Hot |
|
120 VAC | 24 VAC |
Heating Control
H
RC E
R
WM O
YS T A
GT
| Transformer |
| RH | H | ||||
|
|
| ||||||
|
|
| E | |||||
| Hot |
|
|
|
|
| RC | |
120 VAC |
| 24 VAC |
|
| R | |||
|
|
|
|
|
|
| W | M |
|
|
|
|
|
|
|
| O |
|
|
|
|
| Cooling |
| Y | S |
|
|
|
|
| Control |
| ||
|
|
|
|
|
|
| T | |
|
|
|
|
|
|
|
| A |
|
|
|
|
| Fan |
| G | |
|
|
|
|
| Control |
| T |
FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORE- SAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS THERMOSTAT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF THE
5. Press the> button until the temperature setting is at least
3 degrees above room temperature. The heating system should turn on. The fan may not turn on immediately, depending upon the fan delay built into the furnace.
6. Put the |
into the OFF position. The heating |
system should turn off. The fan may |
continue to run for a short period |
of time. |
7. Put the FAN: |
COOL OFF HEAT
FAN: AUTO - ON
Changing Temperature Differential
IMPORTANT: The temperature differential is factory set at 1 (.5°). This means that whenever the room temperature changes by one half of a degree from the temperature setting, the system will turn on. If the system turns on too often, increase the temperature differential.
1. Press both >and> buttons at the same time and hold for one
second. | > | > |
|
|
> | > | COOL OFF HEAT FAN: AUTO - ON |
2. Press either the >or> button to adjust the temperature
System fan does not | Move fan option switch to either |
operate properly. | gas or electric, to match system |
| (see INSTALLATION). |
Thermostat does not display | Check “F” Fahrenheit/”C” Celsius |
proper room temperature. | switch located at top center of |
| circuit board for proper position. |
| If a new selection is made, press |
| “RESET” button located directly |
| below LCD display. |
HEAT/COOL
TWO TRANSFORMER
| (HEATING) |
|
|
|
|
|
| |||
| Transformer |
|
|
|
|
|
| |||
|
|
|
| T |
| |||||
| Hot |
|
|
|
|
|
| RH |
| |
120 VAC | 24 VAC |
|
|
|
| H |
| |||
|
|
|
|
|
|
|
| RC | E |
|
|
|
|
|
|
|
|
|
| R |
|
|
|
|
|
| Heating |
|
| W | M |
|
|
|
|
|
| Control |
|
|
| O |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| Cooling |
|
| Y | S |
|
| Hot |
|
|
| Control |
|
|
| T |
|
|
|
|
|
|
|
|
|
| ||
120 VAC | 24 VAC |
|
|
|
|
| A |
| ||
| Fan |
|
| G |
| |||||
|
|
| T |
| ||||||
|
|
|
|
| Control |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
(COOLING) Transformer
NOTE: Cut center of factory installed jumper and bend back
NOTE: Both transformers must be in phase.
LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above exclusion or limitations may not apply to you.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
the ON position. The blower fan |
should turn on. |
differential up or down.
The display will show:
If problems with thermostat cannot be solved, call:
Technical Support: 608-257-8801
HEAT PUMP WITH | HEAT PUMP WITH |
COOL ACTIVE | HEAT ACTIVE |
REVERSING VALVE | REVERSING VALVE |
8. Put the FAN: |
the AUTO position. The blower fan |
should turn off.
FAN: AUTO - ON
Differential Setting Degrees
11°F/.5°C
22°F/1.0°C
33°F/1.5°C
Monday-Friday 7:45 am-5:00 pm CST
Transformer
Hot
120 VAC | 24 VAC |
Fan
Relay
Compressor
Contactor
Reversing
Valve
|
|
| |
RH | T |
|
|
| Transformer | ||
RC | H | Hot |
|
E |
| ||
| 120 VAC | 24 VAC | |
W | R |
|
|
| M |
| Fan |
G | O |
| |
| Relay | ||
| S |
| Compressor |
Y | T |
| |
| Contactor |
A
OT
B | Reversing |
Valve |
RH T
H
RC
E
R
W
M
GO
S
YT
A
OT
B
The display will return to the room temperature five seconds after the last input.
NOTE: Installer must place jumper | NOTE: Installer must place jumper |
between “W” and “Y” terminals. | between “W” and “Y” terminals. |