draft diverter outlet must be connected to an unobstructed vent of the same size, or larger.

In Canada, CAN/CGA-B149 Installation Code for detailed requirements

In U.S.A., ANSI Z223.1 - NFPA 54, National Fuel Gas Code for detailed requirements.

The vent connection for the 125 HX is 5 inches. However, for installations at high altitude (over 2000 feet above sea level) a six inch vent is required. A 5" by 6" vent adaptor must be affixed to the flue collar of the 125 HX with at least two screws. See fig. 4.

WARNING: Failure TO INCREASE THE VENT SIZE TO SIX INCHES AND/or assure that the manifold pressure

is set to proper value listed for applications at high altitudes will cause unsafe venting, asphyxiation, and will void CSA Certification.

5” X 6” ADAPTOR

USED ON HIGH ALTITUDE

Fig. 4 - Vent Adaptor for High Altitude Installations

GAS CONNECTIONS

NOTE: The 125 HX is supplied with a gas pressure regulator that must be installed on the heater before attaching the gas supply line. See fig. 5. Failure to install the gas regulator as shown in figure 5 will be a violation of CSA certification of the unit. The regulator supplied with the heater is preset for the gas shown on the rating plate to the correct pressure. It is an appliance level regulator designed for (low inlet) pressure (less than 1/ 2 Psig or 15” W.C.)

DO NOT connect to an unregulated or high pressure propane line or to a high pressure commercial natural gas line.

GAS INLET PIPE

PRESSURE TAP

PLASTIC VENT CAP

PRESSURE REGULATOR (with directional arrow on reverse side pointing upward)

Fig. 5 - Installation of Gas Pressure Regulator

The pressure regulator provided with the heater is adjusted to deliver the proper gas pressure (as indicated on the rating plate and in the manual for altitude up to 2000 feet (660 meters) above sea level. On appliances being installed above 2000 ft (660 meters) elevation, the inlet gas pressure should be set at installation to the value shown below.

NOTE: The gas pressures specified below refer to pressures taken at the pressure tap on the gas inlet pipe just above the regulator (See Fig 5). These readings should be taken while the heater is operating at full input

i.e. maximum water flow with the temperature dial selector turned all the way clockwise.

MAXIMUM INLET GAS FLOW PRESSURE SETTING

Altitude

Natural Gas

Liquid Propane

 

inches W.C:

inches W.C:

0' - 2.000 ft

5.7"

10.5"

2.000 ft - 4.500 ft

4.6"

8.4"

Above 4.500 ft consult your local gas provider.

GAS LINE SIZING

-It is strongly recommended that the Natural Gas pipe be Black Iron pipe the entire distance from the outside meter to the inlet of the 125 HX regulator. 1/2” Black Iron pipe up to 10 feet, 3/4” Black Iron pipe up to 40 feet and 1” Black Iron pipe up to 150 feet distances. Flex line tubing is NOT recommended, but if used then oversize it.

-It is strongly recommended that the LP Gas pipe be semi-rigid copper or Black Iron pipe from the outside regulator to the inlet of the 125 HX regulator. For semi- rigid copper piping: 5/8” up to 20 feet and 3/4” up to 60 feet distances. For Black Iron piping: 1/2” up to 45 feet and 3/4” up to 160 feet distances. Flex line tubing is NOT recommended, but if used then oversize it.

THESE FIGURES ARE FOR 125 HX SUPPLY ONLY, ALL OTHER APPLIANCES IN THE BUILDING WILL NEED TO BE INCLUDED IN THE PIPE SIZING.

National Fuel Gas Code requires that a sediment trap (drip leg) be installed on gas appliances not so equipped. The drip leg must be accessible and not subject to freezing conditions. Install in accordance with the recommendations of the serving gas supplier.

WARNING: The heater must be disconnected from the gas supply piping system during any pressure testing of

that system at test pressures in excess of 0.5 psig.

The water heater must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or more than 0.5 psig.

The water heater, including the pressure regulator provided with it, must not be operated at gas supply pressures in excess of 0.5 psig. If overpressure has occurred, such as through improper testing of the gas lines or malfunction of the supply system, the gas valve and regulator must be checked for safe operation. Make sure that the regulator vent is protected against blockage.

When your connections are made, check for gas leaks at all joints (not just the ones you made). Apply some soapy water to all gas fittings and gas valve. Soap bubbles are a sign of a leak.

NOTE: Do not apply soap solution to the pilot or pilot orifice area. If you have a leak, shut off the gas. After verifying that required gaskets are in place, tighten appropriate fittings to stop leak. Turn the gas on and check again with a soapy solution. Never test for gas leaks using a match or flame.

6 720 606 804

9

Page 9
Image 9
AquaStar 125HX NG, 125HX LP specifications GAS Connections, GAS Line Sizing, Adaptor Used on High Altitude

125HX LP, 125HX NG specifications

The AquaStar 125HX NG and 125HX LP are highly efficient gas tankless water heaters designed to meet the demands of modern households. With their compact size and advanced technology, these units provide an endless supply of hot water while maintaining energy efficiency. Both models cater to natural gas and propane applications, making them versatile options for various installations.

One of the standout features of the AquaStar 125HX series is its ability to deliver a powerful output of up to 199,000 BTUs, ensuring that multiple hot water outlets can operate simultaneously without a drop in temperature. Users can enjoy the convenience of hot showers, laundry, and dishwashing all at once, making it an ideal choice for busy families or households with high hot water needs.

These models incorporate a sophisticated modulating gas valve that adjusts the gas flow based on the demand for hot water. This technology not only optimizes energy consumption but also contributes to extended unit life by minimizing wear and tear on the components. The AquaStar 125HX units also come equipped with a patented electronic ignition system, which eliminates the need for a standing pilot light and reduces gas consumption.

Furthermore, the AquaStar 125HX NG and 125HX LP feature a durable heat exchanger constructed from high-grade copper, which enhances thermal efficiency and prevents corrosion. This ensures a longer lifespan and increased reliability for homeowners. Additionally, the units are compact and wall-mounted, allowing for flexible installation in various spaces, including tight utility closets or outside walls.

Safety is also a top priority, with built-in overheat protection and a freeze protection feature that ensures the unit remains operational even in colder climates. The AquaStar 125HX series operates quietly, allowing users to enjoy the benefits of hot water without the disruptive noise commonly associated with traditional water heaters.

In summary, the AquaStar 125HX NG and 125HX LP are leading choices in the tankless water heater market, combining efficiency, reliability, and innovation. Their impressive output, advanced technologies, and compact design make them suitable for modern living, ensuring homeowners have access to hot water whenever they need it. With these features, AquaStar continues to set a high standard in water heating solutions.